Wired Remote Controller - Mitsubishi Electric Mr.SLIM PKA-A12HA4 Service Manual

Split-type, heat pump air conditioners and split-type, air conditioners
Hide thumbs Also See for Mr.SLIM PKA-A12HA4:
Table of Contents

Advertisement

9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
■IR wireless remote controller
CHECK
CHECK
display
ON/OFF
TEMP
ON/OFF
button
FAN
AUTO STOP
MODE
AUTO START
VANE
CHECK LOUVER
CHECK
TEST RUN
button
SET
RESET
CLOCK

■Wired remote controller

ERROR CODE
TEMP.
ON/OFF
MENU
ON/OFF
BACK
MONITOR/SET
DAY
PAR-21MAA
CLOCK
OPERATION
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the temperature
Temperature
buttons.
button
3. Point the remote controller at the
HOUR
sensor on the indoor unit and
button
press the HOUR button.
h
min
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
ERROR CODE
FILTER
CHECK
TEST
ERROR CODE
CLEAR
Turn on the power.
Press the [CHECK] button twice.
Set address with [TEMP] button if system control is used.
Press the [ON/OFF] button to stop the self-check.
CHECK button
Address
TEMP. button
IC : Indoor unit
OC: Outdoor unit
Check code
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
Unit No.
Timer ON/OFF button
<To delete check code>
Display the error code on the self-check result display screen.
The address for self-check will blink when the
button is pressed twice within 3 seconds.
13
13
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation lamp
blinks, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
ON/OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr.slim pka-a18ha4

Table of Contents