Drill A Hole In The Wall; Flaring Work - LG AS-W096URH0/UBH0/UWH0/UMH0 Service Manual

Lg room air conditioner
Table of Contents

Advertisement

Drill a Hole in the Wall

• Drill the piping hole with a ø70mm hole core drill.
Drill the piping hole at either the right or the left with
the hole slightly slanted to the outdoor side.

Flaring Work

Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased
locally.
2. Measure the distance between the indoor and the out-
door unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section
of pipe/tube.
2. Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid drop-
ping burrs into the tubing.
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit,
then put them on pipe/tube having completed burr
removal.
(not possible to put them on after flaring work)
Flaring work
1. Firmly hold copper pipe in a die in the dimension shown
in the table below.
2. Carry out flaring work with the flaring tool.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
A
mm
0~0.5
0~0.5
0~0.5
0~1.0
1.0~1.3
WALL
Indoor
Copper
pipe
90°
Pipe
Point down
Flare nut
Copper tube
Bar
Bar
Copper pipe
Clamp handle
Installation
Outdoor
Slanted Uneven Rough
Reamer
Handle
Yoke
Cone
Red arrow mark
Service Manual 15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents