Daikin RZQ18PVJU Installation Manual page 6

Split system air conditioners
Hide thumbs Also See for RZQ18PVJU:
Table of Contents

Advertisement

DANGER
Do not install unit in an area where fl ammable materials are
present due to risk of explosion resulting in serious injury or
death.
Refrigerant is heavier than air and replaces oxygen. A
massive leak could lead to oxygen depletion , especially in
basements, and an asphyxiation hazard could occur leading
to serious injury or death.
Installation place (unit: inch)
〈Cautions on continuous installation〉
The connection piping outlet direction in the continuous
installation shown in the fi gures below is frontward or down-
ward.
When routing the piping rearward, secure space of 10 in. or
more on the right side of the outdoor unit. (The unit of nu-
meric values below is "inch".)
Make some space for wiring with conduit and servicing
between the units.
(A) When an obstruction is present on the air inlet side
When the upward area is open
(1)
When one outdoor unit is installed individually
When an obstruction is present only on the air inlet
side
When an obstruction is present on the both sides
(2)
When two or more outdoor units are installed side
by side
When an obstruction is present on the both sides
5
When an obstruction is present also in the upward area
(1)
When one outdoor unit is installed individually
When an obstruction is present also on the air inlet
side
When an obstruction is present also on the air inlet
side and both sides
(2)
When two or more outdoor units are installed side
by side
When an obstruction is present also on the air inlet
side and both sides
(B) When an obstruction is present on the air outlet side
When the upward area is open
(1)
When one outdoor unit is installed individually
(2)
When two or more outdoor units are installed side
by side
English