Close Water Systems; Thermal Expansion - A.O. Smith Gdhe 50 Instruction Manual

Power vent/power direct vent residential gas water heaters with hot surface ignitio
Hide thumbs Also See for Gdhe 50:
Table of Contents

Advertisement

close water sYsteMs

Water supply systems may, because of code requirements or such
conditions as high line pressure, among others, have installed
devices such as pressure reducing valves, check valves, and back
flow preventers. Devices such as these cause the water system to
be a closed system.

therMal eXpansIon

As water is heated, it expands (thermal expansion). In a
closed system the volume of water will grow when it is heated.
As the volume of water grows there will be a corresponding
increase in water pressure due to thermal expansion. Thermal
expansion can cause premature tank failure (leakage). This
type of failure is not covered under the limited warranty.
Thermal expansion can also cause intermittent temperature-
pressure relief valve operation: water discharged from the
valve due to excessive pressure build up. This condition is
not covered under the limited warranty. The temperature-
pressure relief valve is not intended for the constant relief of
thermal expansion.
A properly sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion.
fIGure 9.
note: to protect against untimely corrosion of hot and cold
water fittings, it is strongly recommended that di-electric unions
or couplings be installed on this water heater when connected
to copper pipe, see figure 10 also.
Figures 9 and 10 show the typical attachment of the water piping to
the water heater. The water heater is equipped with 3/4 inch NPT
water connections.
note: If using copper tubing, solder tubing to an adapter before
attaching the adapter to the water heater connections. do not
solder the water lines directly to the water heater connections.
It will harm the dip tube and damage the tank.
t & p valve and pipe Insulation (if supplied)
1. Locate the temperature and pressure relief valve on the water
heater (also known as a T&P relief valve). See Figure 11.
2. Locate the slit running the length of the T&P relief valve insulation.
3. Spread the slit open and fit the insulation over the T&P relief
valve. See Figure 11. Apply gentle pressure to the insulation
to ensure that it is fully seated on the T&P Relief Valve. Once
seated, secure the insulation with duct tape, electrical tape, or
equivalent. IMPORTANT: The insulation and tape must not block
the discharge opening or hinder access to the manual relief lever
(Figure 11). Ensure a discharge pipe is installed into the T&P
valve discharge opening per the instructions in this manual.
4. Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.
5. Locate the slit running the length of a section of pipe insulation.
6. Spread the slit open and slip the insulation over the cold water
(inlet) pipe. Apply gentle pressure along the length of the insulation
to ensure that it is fully seated around the pipe. Also, ensure that the
base of the insulation is flush with the water heater. Once seated,
secure the insulation with duct tape, electrical tape, or equivalent.
7. Repeat steps 5 and 6 for the hot water (outlet) pipe.
8. Add additional sections of pipe insulation as needed.
16
fIGure 10.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents