SPECIFICATION

3
3-1. Specification
Model
Power source
Cooling capacity ❇ 1
Heating capacity ❇ 1
Cooling
Power consumption
(50/60Hz)
Heating
Cooling
Current
Heating
External finish
Height
Dimension
Width
Depth
Net weight
Heat exchanger
Type
Airflow rate
(Lo-Hi)
Fan
External static
220V
pressure ❇2
230, 240V
Type
Motor
Output ❇ 3
Air filter (option)
Gas
(Flare)
Refrigerant
pipe dimension
Liquid
(Flare)
Drain pipe dimension
Noise level (Lo-Hi)
220V
230, 240V
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27°CDB/19 °CWB,Outdoor 35°CDB (WR2: water 30°C)
Heating : Indoor 20°CDB,Outdoor 7°CDB/6°CWB
❇ 2 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
❇ 3 The value are that at 240V.
PEFY-P40VMH-E PEFY-P50VMH-E
kW
4.5
kW
5.0
kW
0.19/0.23
kW
0.19/0.23
A
0.88/1.06
A
0.88/1.06
mm
mm
mm
kg
44
Cross fin (Aluminum plate fin and copper tube)
m
/min
10.0-14.0
3
Pa
Pa
kW
0.08
Synthethic fiber unwoven cloth filter(long life)
mm
ø
12.7
mm
ø
6.35
dB(A)
27-34
dB(A)
31-37
PEFY-P63VMH-E
220-240V 50Hz /60Hz
~
5.6
7.1
6.3
8.0
0.24/0.30
0.24/0.30
1.12/1.38
1.12/1.38
Galvanizing
380
750
900
45
Sirocco fan✕
1
13.5-19.0
50/100/200
100/150/200
Single phase induction motor
0.12
ø 12.7(R410A)
ø 15.88(R22,R407C)
ø 6.35(R410A)
ø 9.52(R22,R407C)
32 (1-1/4 inch)
32-38
36-41
(WR2: water 20°C)
PEFY-P71VMH-E
8.0
9.0
0.26/0.33
0.26/0.33
1.20/1.51
1.20/1.51
1000
50
15.5-22.0
0.14
ø 15.88
ø
9.52
32-39
35-41
6