(3) Checking procedure.
No.
Procedure
1
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
2
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
3
Start the operation with the system
which the time of the restart delay
timer is shortened.
4
Make the operation status by
pressing once the [ ] button.
1. The time of the restart delay timer
is shortened.
2. Cool operation
3. Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5. Continuous operation.
5
The status of No. 4 is continued, and
make the following condition.
1. Heat operation
2. Make the setting temperature
higher enough than room
temperature.
6
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1. Operation [Cooling]
2. Airflow [High fan]
3. Continuous operation
Table 11-6-1
Check Point (Symptom)
1. Is the fuse blown?
Voltage check
1.Between F01 and CN01(pin1)
(AC 220 ~ 240 V)
2.Between + and − of C03
(DC310 ~ 340V)
3. Between
and
5V
GND
4. Between
and
12V
GND
1. All indicators light for 3 sec..
2. Indicators do not indicate normally
after approximate 3 sec..
1. Compressor does not operate.
2. OPERATION lamp blinks.
1. Compressor does not operate.
2. OPERATION lamp blinks.
1. Motor does not rotate. (The key
operation is accepted.)
2. The Motor rotates, but it vibrates
too much.
– 71 –
FILE NO. SVM-07009
Causes
1. Application of shock voltage.
Overload by short-circuit of the
parts.
1. AC power cord is defective.
Poor contact of the terminal plate.
2. Capacitor (C121) is defective.
Line filter (L01) is defective.
Capacitor (C03) is defective.
Diode (D01, D02, D03 or D04)
is defective.
3. T101 is defective.
}
Defective indicator, or poor
housing assembly.
(CN21)
1. The temperature of the indoor
heat exchanger is abnormally
lower.
2. Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN62)
3. Heat exchanger sensor, main
P.C. board are defective. (Refer to
4. Main P.C. board is defective.
1. The temperature of the heat
exchanger is abnormally high.
2. The heat exchanger sensor
connector has short-circuit. (CN62)
3. The heat exchanger sensor is
defective.
4. P.C. board is defective.
1. Poor contact of the motor
connector.
2. Fan motor is defective

Hide quick links: