Indoor Unit (Ras-13Ukhp-E2, Ras-10Ukhp-E) - Toshiba RAS-13UKHP-E2 Service Manual

Air conditioner split wall type
Table of Contents

Advertisement

4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-13UKHP-E2, RAS-10UKHP-E2)
No.
Parts name
1
Fan motor (for indoor)
2
Thermo sensor (TA-sensor)
3
Switching transformer (T01)
4
Microcontroller unit (IC30)
5
Heat exchanger sensor
(TC-sensor)
6
Line filter (L01)
7
Bridge rectifier (DB01)
8
Capacitor (C02)
9
Fuse (F01)
10
Varistor (R21, R22)
11
Resistor (R01)
12
Louver motor
13
Relay (Comp., RY01)
14
Relay (Fan, RY03)
15
Relay (Solenoide, RY04)
4-2. Outdoor Unit (RAS-13UAH-E2)
No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve)
6
Overload relay
Type
MMF-240-20-4A-1
———
SWT-47
TMP87CM40AN
———
LC*SS11V-06270
D3SBA60
KMH400VSSN47M22S
TSCR6.3A
15G561K
RF-2TK5R6
MP24GA
DI12D1
G5N-1A
G5N-1A
Type
Output (Rated) 1100 W, 2 poles, 1 phase, 220 – 240 V, 50Hz
PH170T2-4L2
Winding resistance (Ω)
(at 20°C)
Output (Rated) 42 W, 6 poles, 1 phase, 220 – 240 V, 50Hz
HF-240-42A
Winding resistance (Ω)
(at 20°C)
DS45115CBPQC AC 450 V, 1.5µF
DS371356CPN
AC 370 V, 35µF
VHV-01AJ503C1
AC 220 – 240 V, 50Hz
JMRA99257-9200 U/T : 8.0A (80°C), OPEN : 145±5°C, CLOSE : 75±11°C
– 12 –
FILE NO. SVM-03004(1)
Specifications
AC Motor with 135°C thermo fuse
10kΩ at 25°C
10kΩ at 25°C
27mH, 600mA
4A, 60 V
47µF, 400 V
T6.3A, 250VAC
560 V
5.6Ω, 2 W
12VDC
Rating 20A/AC250 V, 12VDC
Rating 3A/AC250 V, 12VDC
Rating 3A/AC250 V, 12VDC
Specifications
C-R
2.22
Red-Black
176.2
C-S
3.04
White-Black
290.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents