New Or Replacement Line Set - Lennox Elite XC16 Installation Instructions Manual

Elite series
Hide thumbs Also See for Elite XC16:
Table of Contents

Advertisement

2. With a continuous motion slightly rotate and guide the
lip of top tab inward as illustrated in figure 12, details
A and C, then upward into the top slot of the hinge
corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel's hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
5. When panel is correctly positioned and aligned, insert
the screws and tighten.

New or Replacement Line Set

This section provides information on installation or
replacement of existing line set. If line set are not being
installed then proceed to Brazing Connections on page 9.
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. Also, consider the following when
placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed in table 2.
Table 2. Refrigerant Line Set
Field Connections
Model
Liquid
Suction
Line
Line
3/8".
3/4"
−024
(10 mm)
(19 mm)
−036
3/8".
7/8"
−048
(10 mm)
(22 mm)
3/8".
1−1/8".
−060
(10 mm)
(29 mm)
NOTE − When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical
Support Product Applications for assistance. To obtain the
correct information from Lennox, be sure to communicate
the following points:
S
Model (XC16) and size of unit (e.g. −060).
S
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S
Number of elbows and if there is a rise or drop of the
piping.
506101−01 07/09
Recommended Line Set
Liquid
Suction
L15 Line Set
Line
Line
L15−41
3/8"
3/4"
15 ft. − 50 ft.
(10 mm)
(19 mm)
(4.6 m − 15 m)
L15−65
3/8"
7/8"
15 ft. − 50 ft.
(10 mm)
(22 mm)
(4.6 m − 15 m)
3/8"
1−1/8"
Field
(10 mm)
(29 mm)
Fabricated
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was
metered
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.
If the XC16 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served
as a metering device (RFCI), the liquid line must be
replaced prior to the installation of the XC16 unit. Typically
a liquid line used to meter flow is 1/4" in diameter and
copper.
INSTALLING LINE SET
Line
Set
Isolation This
procedures, which ensure proper refrigerant line set
isolation:
S
Installation of line set on vertical runs is illustrated in
figure 14.
S
Installation of a transition from horizontal to
vertical is illustrated in figure 15.
S
Installation of line set on horizontal runs is
illustrated in figure 16.
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION
PRACTICES SHOULD BE USED
IF LINE SET IS TO BE INSTALLED
ON EXTERIOR OF OUTSIDE
WALL.
OUTSIDE
WALL
PVC PIPE
Figure 14. Refrigerant Line Set: Installing
Vertical Runs (New Construction Shown)
Page 8
into
the
evaporator
reference
SUCTION LINE
SLEEVE
SUCTION LINE WRAPPED WITH
ARMAFLEX
LIQUID LINE
IMPORTANT! REFRIGERANT
LINES MUST NOT CONTACT
STRUCTURE.
CAULK
FIBERGLASS INSULATION
by
utilizing
illustrates
LIQUID
LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents