Rear Wall Vent Installation - Monessen Hearth MDV500, MDV600 Installation & Operating Instructions Manual

Mdv series direct vent gas fireplace
Hide thumbs Also See for MDV500, MDV600:
Table of Contents

Advertisement

VentIng InstallatIon     
rear wall Vent InstallatIon 
(5" 
8" VentIng only)
x
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance. Only an MHSC brand termination
is allowed for this application.
The maximum horizontal distance between the rear
of the appliance and the termination is 20" (508 m).
Figure 14.
Only one 45° elbow is allowed in these installations.
rear Vent top View
20"
(508 mm)
Max.
Figure 14 -
Rear Vent Application,
Maximum Horizontal Distance
1. Rigid vent pipes and fittings have special twist-lock
connections. Assemble the desired combination of pipe
FP1188
and elbows to the appliance adapter.
rear wall install
twist-lock procedure: The female ends of the pipes
and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push the
pipe sections together and twist one section clockwise
approximately one-quarter turn until the sections are
fully locked. Figure 15
note:  sealant is not required to assemble fireplace 
venting. do not use silicone sealant at the inner flue 
exhaust connections.
note: horizontal runs of 
vent  must  be  supported 
every 3' (914 mm). use wall 
straps for this purpose. 
Figure 15 -
Rigid Vent Pipe
Connections
75D2523
FP1953
20"
(508 mm)
Max.
FP1188
Female
Locking Lugs
Male Slots
FP1953
MDV Series Direct Vent Gas Fireplace
2. Refer to the venting and termination instructions for
further instructions.
3. Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening.
 
combustible Interior walls: Cut a 12Z\x"H x 10Z\x" W
(318 x 267 mm) hole through the interior wall.
 
combustible exterior walls: Cut a 10Z\x"H x 10Z\x"W
(267 x 267 mm) square hole through the exterior
wall frame. Figure 16
 
noncombustible walls: Hole opening should be 8Z\x"
(216 mm) in diameter.
10Z\x"
(267 mm)
10Z\x"
(267 mm)
combustible wall
8Z\x"
(216 mm)
Figure 16 -
Exterior Wall Framing Dimensions
4. The center of the hole should align with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 16
VO584-100
5. Apply a bead of non-hardening mastic around the
Vent Opening
outside edge of vent cap. Position the vent cap in the
center of hole on the exterior wall with the word "UP"
2/99 djt
on the vent cap facing up. Insure proper clearance of
1" to combustibles is maintained. Attach the vent cap
with four wood screws supplied. Figure 17
note: Replace the wood screws with appropriate fasteners
for stucco, brick, concrete, or other types of siding.
For vinyl siding, stucco, or wood exterior use vinyl siding
standoffs between vent cap and exterior wall for Simpson
or Selkirk Terminations only. The vinyl siding standoff pre-
vents excessive heat from melting the vinyl siding material.
note: MHSC Termination does not require standoff. Bolt
the vent cap to the standoff or wall. Apply non-hardening
mastic around outside edge of the standoff instead of the
vent cap assembly. Use wood screws provided to attach
the standoff. Figure 18
framing
VO584-100
17