Haier AS09/12GS2ERA Service Manual page 18

Wall mounted type dc inverter em-series
Table of Contents

Advertisement

Manus: When the system is operating, you can set the high, medium or low speed manually. ( When
the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) and
the temperature of the indoor coils has been below zero centigrade for 10 seconds, the compressor
will be stopped and the malfunction will be recorded in the malfunction list. The indoor system will
continue to run. When the temperature of the indoor coil is raised to 7 , the compressor wil l be
restarted again (the prerequirement of 3 minutes' delay should be satisfied.)
* timing system on/off function.
* Dormant control function.
5.1.3 Demoisture mode.
* temperature control range: 16---30
* temperature difference:
Control feature: send the demoisture signal to the outdoor system.
When Tr>Ts+2 , the compressor will be turned on, the indoor fan will operate at the set speed.
When Tr is between the Ts and Ts+2 , the outdoor system will operate at the high demoisture
frequency for 10 minutes and then at the low demoisture mode for six minutes. The indoor fan
will operate at low speed.
When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option.
All the frequency converses have a ±1
* Wind speed control: Automatic:
When Tr >= Ts+ 5 , high speed.
When Ts+3
When Ts+2
When Tr<Ts+2 , light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the
system will be changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be
delayed for 3 minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3 , the manual operation can not be made. (obligatory
automatic operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM)
and the temperature of the indoor coils has been below zero centigrade for 10 seconds, the
compressor will be stopped and the malfunction will be recorded in the malfunction list. The
indoor system will continue to run. When the temperature of the indoor coil is raised to 7 , the
compressor will be restarted again (the prerequirement of 3 minutes' delay should be satisfied.)
* coil protection (synchronic overheating protection) are installed for the four directions latch
malfunctions when demoisturing.
* timing system on/off function.
AS09/12GS2ERA 1U09/12BS1ERA-SM
1
Tr< Ts+5 , medium speed.
Tr< Ts+3 , low speed.
difference.
15
Function and control
Domestic Air Conditioner

Advertisement

Table of Contents
loading

This manual is also suitable for:

1u09/12bs1eraAs09gs2eraAs12gs2era1u09bs1era1u12bs1era

Table of Contents