Carrier 53DFS250-HW Installation Manual page 7

Thermostat
Hide thumbs Also See for 53DFS250-HW:
Table of Contents

Advertisement

Installer setup
Setup
Number
Setup Name
Date (Year Upper)
0120
Date (Year Lower)
0130
Date (Month)
0140
Date (Day)
0150
Schedule Options
0160
System Selection
0170
Pre-occupancy Purge
0185
Duration
Cycles Per Hour (CPH)
0220
for first stage cooling/
compressor
0270
Cycles Per Hour (CPH) for
heating first and second
stage
Continuous Backlight
0280
Changeover
0300
Deadband
0310
Temperature Indication
0320
Scale
Daylight Saving Time
0330
Remote Temp Sensor/
0340
Remote Setback/
Changeover Input
Remote Temp Sensor/
0340
Remote Setback/
(Non-
Changeover Input
program-
mable)
Delay for Remote Setback
0341
Override Option (only
0342
available in non-
programmable mode)
Unoccupied Heating
0343
Setpoint (only when remote
setback enabled)
Settings & Options (factory default in bold)
20 (2011-2078)
21 (2101-2178)
08 (2008)
[Other options: 00-99]
6 [Other options: 1-12]
15 [Other options: 1-31]
4
Programmable
0 Non-programmable
1 Cooling only
2 Heat pump plus electric heat
0 No duration
[Other options: 1, 2, or 3 hours]
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
9 Recommended
[Other options: 1–12 CPH]
0
No
1
Yes
1
Auto
0 Manual
3 3°F (2.0°C)
°F (1.5–5.0°C)
[Options: 2–9
0 °F
1 °C
1 ON
0 OFF
0
None
1 Remote 10K Indoor
2 Remote 20K Indoor
0
None
1 Remote 10K Indoor
2 Remote 20K Indoor
5 Remote Setback, normally open
6 Remote Setback, normally closed
0 No Delay
2 2 Minute Delay
1 Override
0 No Override
60 60°F (15.5°C)
[Options: 50–65
7
53DFS250-HW
]
°F (10–18°C)
]
Continued on next page
69-2565—05

Hide quick links:

Advertisement

Table of Contents
loading