Carrier WeatherMaker 50TCQ Product Data page 68

Packaged heat pump 3 to 12.5 nominal tons
Table of Contents

Advertisement

Table 54 – 50TCQD12
VOLTAGE RANGE
V ---Ph---Hz
MIN
MAX
208--- 3--- 60
187
253
230--- 3--- 60
187
253
460--- 3--- 60
414
506
575--- 3--- 60
518
633
Table 55 – 50TCQD14
VOLTAGE RANGE
V ---Ph---Hz
MIN
MAX
208--- 3--- 60
187
253
230--- 3--- 60
187
253
460--- 3--- 60
414
506
575--- 3--- 60
518
633
ELECTRICAL INFORMATION (cont.)
2- - Stage Cooling
COMP (Cir 1)
COMP (Cir 2)
RLA
LRA
RLA
15.6
110
15.9
15.6
110
15.9
7.7
52
7.7
5.8
39
5.7
2- - Stage Cooling
COMP (Cir 1)
COMP (Cir 2)
RLA
LRA
RLA
22.4
149
22.4
22.4
149
22.4
10.6
75
10.6
8.5
54
8.5
OFM (ea)
LRA
WATTS
FLA
110
800
6.2
110
800
6.2
52
800
3.1
39
800
2.5
OFM (ea)
LRA
WATTS
FLA
149
325
1.5
149
325
1.5
75
325
0.8
54
325
0.7
68
10 TONS
IFM
EFF at
TYPE
FLA
Full Load
STD
80%
5.2
MED
80%
10
HIGH
80%
15
STD
80%
5.2
MED
80%
10
HIGH
80%
15
STD
80%
2.6
MED
80%
4.4
HIGH
80%
7.4
STD
80%
2
MED
80%
2.8
HIGH
81%
5.6
12.5 TONS
IFM
EFF at
TYPE
FLA
Full Load
STD
80%
7.5
MED
80%
7.5
HIGH
84%
17.0
HIGH
89.5%
20.4
High Eff.
STD
80%
7.5
MED
80%
7.5
HIGH
88%
15.0
HIGH
89.5%
20.4
High Eff.
STD
80%
3.4
MED
80%
3.4
HIGH
88%
7.6
HIGH
89.5%
10.2
High Eff.
STD
80%
2.8
MED
80%
2.8
HIGH
88%
6.1
HIGH
89.5%
9.0
High Eff.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents