NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
** Total system kW is total of indoor and outdoor unit kilowatts.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80˚F (27˚C) entering air at the indoor coil. For sensible capacities at other than 80˚F (27˚C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80˚F (27˚C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80˚F (27˚C).
When the required data fall between the published data, interpolation may be performed.
CONDENSER ENTERING AIR TEMPERATURES deg F
85
Total
Capacity
Capacity
Sys-
MBtuh{
MBtuh{
tem
Total
Sens}
Total
KW**
24ABA360A30 Outdoor Section With CAP**6024A** Indoor Section
64.56
34.48
4.58
61.30
59.24
42.75
4.53
56.25
54.45
50.95
4.49
51.79
53.42
53.42
4.48
51.22
65.46
36.09
4.69
62.07
60.11
45.38
4.64
57.00
55.57
54.47
4.59
52.95
55.35
55.35
4.59
52.99
66.10
37.62
4.79
62.61
60.73
47.89
4.74
57.53
56.90
56.90
4.70
54.41
56.90
56.90
4.70
54.42
Multipliers for Determining the Performance With Other Indoor Sections