Dimensions (mm)
Weight (kg)
Airflow (m3/min)
Nominal sound level (dBA)
Low noise mode (dBA) @ 7°C
Guaranteed operating range
Electrical Supply
Phase
Running current (A) [Max]
Fuse Rating (A)
Heating A2/W35
Heating A7/W35
Primary Flow Rate
PUHZ-W50VHA-BS
Width
Depth
Height
(Outdoor)
Capacity (kW)
COP
Power Input (kW)
Nominal Flow Rate (L/min)
Capacity (kW)
COP
Power Input (kW)
Nominal Flow Rate (L/min)
Maximum (L/min)
Minimum (L/min)
Nominal Conditions
Outside air temperature (dry)
Outside air temperature (humid)
Water temperature (inlet/outlet)
* Grille
◊ At distance of 1m from the outdoor unit
PUHZ-W50VHA-BS
950
330+30*
740
64
50
45 ◊
40
- 15 ~ +35°C
220-240v, 50Hz
Single
5.4 [13]
16
5.0
3.13
1.6
14.3
5.0
4.1
1.22
14.3
25.8
10
A2 / W35
A7 / W35
2°C
7°C
1°C
6°C
30 / 35°C
30 / 35°C
7