Tekmar 527 Installation & Operation Manual

Tekmar 527 Installation & Operation Manual

Hide thumbs Also See for 527:

Advertisement

tekmarNet
®
2 Thermostats 527, 528, 530
Installation & Operation Manual
Introduction
This Installation and Operation Manual includes detailed wiring instructions, settings and operational features of the
®
tekmarNet
2 Thermostats 527, 528 and 530. These 2-wire thermostats are part of a complete tekmarNet
OUTDOOR
F
FLOOR
F
HEAT
Thermostat 527
One Stage Heat
Cooling Group Member
Dual Temperature Display
Simple Temperature Adjustment
Thermostat 528
One Stage Heat
Cooling Group Member
Auxiliary Sensor Input
Floor Minimum & Maximum
Dual Temperature Display
Local Override Button
Thermostat 530
One-Stage Heat
One Stage Cool
Fan Operation
Cooling Group Master
Dual Temperature Display
Local Override Button
1 of 28
Features
®
tekmarNet
communications compatibility
Simple 2-wire connectivity
Schedule member
Optimum start
Scenes
Outdoor temperature display
Freeze protection
Cooling groups
Exercising
Zone synchronization
Large LCD with backlight
CSA C US approved for use in USA
and Canada
Benefits
Energy savings
Reduced temperature swings
Suitable for 2-wire retrofits
Compatible with tekmarNet Timers,
User Switches and Gateway for
additional control options
Interlock to prevent simultaneous
heating & cooling
Note
tN2 Zone Manager, Expansion Module
Wiring Center or House Control
required for operation
© 2009
D 527
06/09
®
system.
D 527 - 06/09

Advertisement

Table of Contents
loading

Summary of Contents for Tekmar 527

  • Page 1 Introduction This Installation and Operation Manual includes detailed wiring instructions, settings and operational features of the ® ® tekmarNet 2 Thermostats 527, 528 and 530. These 2-wire thermostats are part of a complete tekmarNet system. Features Thermostat 527 ® •...
  • Page 2: Table Of Contents

    ® Address ..........22 Button Operation ........... 10 Cool Group Master (530 Only) ......23 Setting the Temperature ........10 Cool Group Member (527 and 528 Only) ....23 User Settings ............11 Troubleshooting Guide ..........24 Adjust Menu ............12 Testing the Wiring ............
  • Page 3: Caution

    An approved circuit breaker or power disconnect that de-energizes the high voltage wiring should be located near the Zone Manager, and marked as the 115 V (ac) power disconnect for this device. 3 of 28 © 2009 D 527 - 06/09...
  • Page 4: Rough-In Wiring

    Stud 007 Adaptor Stud Plate Thermostat Base Thermostat Switch Base Thermostat Thermostat ” (83 mm) Wall ” ” (60 mm) (60 mm) screwhole screwhole Mounted on switch box Mounted on wallboard © 2009 D 527 - 06/09 4 of 28...
  • Page 5: Thermostat Displays

    This display shows all potential symbols that may show up on your thermostat. They will be referred to throughout this manual, so it is a good idea to become familiar with those that are applicable to your thermostat model (527, 528 or 530).
  • Page 6: 527 Thermostat

    527 Thermostat Wiring The Thermostat 527 operates a single hydronic heating system zone. 527 tNt tNt 527 One Stage Heat For instructions see brochure Reset Menu Use at least 65°C conductors Made in Item Zone Canada Module 1 2 3 4...
  • Page 7: Button Operation

    Press the or the button to select the desired The Away temperature cannot be changed temperature for the current operating temperature. The temperature range is from 40°F (4.5°C) to 85°F (29.5°C). 7 of 28 © 2009 D 527 - 06/09...
  • Page 8: User Settings

    Synchronization • There is no tekmarNet ® System Control on the system. STEP 5 The large number shows the type number as 527. View Type and Software The software version is shown in the upper right hand corner. Version ®...
  • Page 9: 528 Thermostat

    528 One Stage Heat Thermostat 528 DIP Switches For instructions see brochure Use at least 65°C conductors Made in 1 2 3 4 Canada 1 2 3 4 9 of 28 © 2009 D 527 - 06/09...
  • Page 10: Button Operation

    If a symbol does not appear, there is no schedule available. Schedules are provided by tekmarNet ® Timers or Thermostats that are connected to the Zone Manager, Expansion Module or Wiring Center. © 2009 D 527 - 06/09 10 of 28...
  • Page 11: User Settings

    STEP 5 The address can be returned to automatic “Au” between addresses 24 and 1. Manually Change tekmarNet ® Address Ensure to document the address number when manually addressing thermostats. 11 of 28 © 2009 D 527 - 06/09...
  • Page 12: Adjust Menu

    Room Sensor setting in the Adjust menu is set to On AND Default = 85°F (29.5°C) • A slab sensor is installed on the auxiliary sensor input AND • Switch setting 4 is set to Floor (On position). Continued on next page. © 2009 D 527 - 06/09 12 of 28...
  • Page 13 Thermostat can follow schedule 1, 2, 3, or 4. Default = 1 Available when: • Switch setting 1 is set to Setback (On Position). After the last item, the control returns to the first item in the Adjust menu. 13 of 28 © 2009 D 527 - 06/09...
  • Page 14: 530 Thermostat

    One Stage Cool / One Fan Thermostat 530 DIP Switches Relays: 24V (ac) 2A For instructions see brochure Use at least 65°C conductors Made in 1 2 3 4 Canada 1 2 3 4 © 2009 D 527 - 06/09 14 of 28...
  • Page 15: Button Operation

    If a symbol does not appear, there is no schedule ® available. Schedules are provided by tekmarNet Timers or Thermostats that are connected to the Zone Manager, Expansion Module or Wiring Center. 15 of 28 © 2009 D 527 - 06/09...
  • Page 16: User Settings

    STEP 5 The address can be returned to automatic “Au” between addresses 24 and 1. Manually Change tekmarNet ® Address Ensure to document the address number when manually addressing thermostats. © 2009 D 527 - 06/09 16 of 28...
  • Page 17: Adjust Menu

    VENTILATION OFF, On Select whether or not ventilation is required. When turned On, fan Default = OFF operation can be customized with the next two Fan settings. Continued on next page. 17 of 28 © 2009 D 527 - 06/09...
  • Page 18 Thermostat can follow schedule 1, 2, 3, or 4. Default = 1 Available when: • Switch setting 1 is set to Setback (On Position). After the last item, the control returns to the first item in the Adjust menu. © 2009 D 527 - 06/09 18 of 28...
  • Page 19: Sequence Of Operation For All Tn2 Thermostats

    A percent run time can be selected if Ventilation is set On in the Adjust Menu. “Auto” is equivalent to Off when in Vent Mode. 19 of 28 © 2009 D 527 - 06/09...
  • Page 20: Schedules (Requires Schedule Device)

    Communication System schedules. Thermostats 528 and 530 can follow system Control schedule 1, 2, 3, or 4. Thermostat 527 can only follow system schedule 1. Optimum Start When a programmable schedule is selected, there is a time The Optimum Start applies for both the heating and the...
  • Page 21: Cycles Per Hour / Synchronization

    System Control, the Heating Cycles Per Hour setting in the Adjust menu allows the installer to select Auto or Sync. Indoor Temperature Feedback The 527, 528 and 530 Thermostats can provide indoor Indoor Temperature Feedback also allows the room temperature feedback to a tekmarNet ®...
  • Page 22: Thermal Motor Zone Valves

    Delay setting is located in the Adjust Menu of 528 or 530 open before the system pump is turned on. If the thermostat thermostats. It is located on DIP switch 4 of a 527. Backlight The backlight can be adjusted using the “lite” setting. Select backlight for 30 seconds after a button is pressed.
  • Page 23: Cool Group Master (530 Only)

    The cool group master operates the cooling equipment for the group. Thermostats 527 and 528 can be To join “Cool Group 1”, set switch 3 to “Cool Member 1” members of ‘Cool Group 1’, allowing them to be included (down).
  • Page 24: Troubleshooting Guide

    The built-in air temperature sensor has a short circuit fault. If a floor sensor is present (Thermostat 528 only), heating will operate to satisfy floor min. This error cannot be field repaired. Contact your wholesaler or tekmar sales representative for details on the repair procedures.
  • Page 25: Testing The Wiring

    A good quality electrical test meter, capable of reading from at least 0-300 V (ac), 0-2,000,000 Ohms, and testing for continuity is essential to properly test the wiring and sensors. 25 of 28 © 2009 D 527 - 06/09...
  • Page 26: Cleaning The Thermostat

    0 V (ac). This thermostat is not compatible Center are operating correctly. The thermostat may with 24 V (ac) equipment. have a fault. Contact your local tekmar representative for assistance. 3. Use an electrical test meter to measure DC voltage between the tN2 terminals for 20 seconds.
  • Page 27: Warranty

    NTC thermistor, 10 kΩ @ 77°F (25°C ± 0.2°C) ß = 3892 – Included None – Optional tekmar type # 071, 070, 072, 073, 076, 077, 078, 079, 082, 083, 084 ® tekmarNet 2 Thermostat 530: One Stage Heat, One Stage Cool, One Fan Control Microprocessor PID control;...
  • Page 28 Purchaser shall indem- such Product sale and acknowledges that it has read nify and hold tekmar harmless from and against any and all and understands same. claims, liabilities and damages of any kind or nature which...

This manual is also suitable for:

528530

Table of Contents