CONDENSING UNIT SPECIFICATIONS
Nominal Cooling Capacity, BTUH
Compressor
R.L. Amps
L.R. Amps
Condenser Fan Motor
Horsepower
F.L. Amps
Refrigerant Line Size
Liquid Line, Inches O.D.
Suction Line, Inches O.D.
Refrigerant Connection Size
Liquid Valve Size O.D.
Suction Valve Size O.D.
Refrigerant Charge
Power Supply
(1)
Minimum Circuit Ampacity
Maximum Overcurrent Device
Electrical Conduit Size
Power Supply (Inches)
Approximate Shipping Weight
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
(3)
Installer will need to supply 3/4" to 7/8" adapters for suction line connectors
(4)
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
8
GSC130363B*
GSC130483B*
36,000
48,000
9.0
65.5
1/6
1.1
3/8"
7/8"
1-1/8"
3/8"
3
3/4"
7/8"
83
208/230-60-3
208/230-60-3
12.4
(2)
20
1/2 or 3/4
1/2 or 3/4
214
GSC130603B*
57,000
12.4
14.7
88.0
91.0
1/4
1/4
1.5
1.5
3/8"
3/8"
1-1/8"
3/8"
3/8"
4
4
7/8"
89
131
208/230-60-3
17
19.9
20
30
1/2 or 3/4
207
242
GSC130484B*
GSC130604B*
45,500
55,500
5.8
7.1
44.0
50.0
1/4
1/4
0.8
0.8
3/8"
3/8"
1-1/8"
1-1/8"
3/8"
3/8"
4
4
7/8"
7/8"
102
131
460-60-3
460-60-3
8
9.7
15
15
1/2 or 3/4
1/2 or 3/4
207
242