OPTIOnAL BLOWeR InSTALLATIOn InSTRUCTIOnS

INSTALLING OPTIONAL BLOWER SRB-18 OR SRB-30
If heater is installed onto the wall, in order to install the optional
blower, the heater must be removed from the wall. If heater is in-
stalled on optional floor stand there is adequate access area avail-
able to install the optional blower.
1.
Turn "OFF" gas supply to the heater.
2.
Remove lower louver from casing assembly (2 screws).
3.
Remove reflector from casing assembly (2 screws).
4.
Remove upper louver from casing assembly (2 screws).
5.
Remove on/off switch knockout from the casing assembly
top.
6.
Insert the on/off switch wires through the casing assembly
top. The on/off switch wires will enter the top portion of the
casing assembly. Snap on/off switch into the casing assembly
top.
7.
Route cord set through 9/16" (14mm) diameter hole on casing
assembly back. Insert approximately 3" (76mm) of cord set
into casing assembly back.
8.
When you are facing the front of the heater, position the
optional blower assembly onto the top heat shield of the
heater. The motor wire harness should be facing into the top,
right portion of the heater.
9.
Attach (1) pin terminal from black (hot) wire, smooth
insulation on cord set to (1) socket terminal from the on/off
switch.
10. Attach (1) pin terminal from black (neutral) wire, ribbed
insulation on cord set to (1) socket terminal from white
(neutral) wire on motor wire harness.
Page 24
OPTIONAL BLOWERS
SRB-18 and SRB-30
for Unvented Room Heaters SR-18 and SR-30
HEAT SHIELD
SR-30 Shown
11. Attach (1) pin terminal from the on/off switch to (1) socket
terminal from black (hot) wire on motor wire harness.
12. Attach the green ground wire from the motor wire harness
and the green ground wire from the cord set to the bottom
right side of the blower housing with (1) screw provided with
the optional blower.
13. With the heater standing upright, position the air discharge
opening of the blower housing downward. Place the bottom
flange of the blower housing over the top edge of the top heat
shield. Insert the blower housing into the top portion of the
heater by pivoting the blower housing upward 90°. Attach
the blower housing to the casing assembly with (4) screws
provided with the optional blower.
14. Grasp cord set at casing assembly back and pull excess cord
set through casing assembly back. Secure cord set in casing
assembly back with the strain relief provided with the optional
blower.
15. Installation of optional blower is completed.
16. If heater was removed from the wall, in order to install
optional blower, check for gas leaks at all gas connections
before lower louver is replaced onto casing assembly.
Attention! After optional blower has been installed use the
following steps to properly align the upper louver and the reflector
with the heat shield.
A. When replacing upper louver, be sure the bottom lip of upper
louver goes behind the heat shield.
B. When replacing reflector, be sure the top lip of reflector goes
in front of the heat shield.