HEATING CAPACITY
PUHZ-RP200YHA/PUHZ-RP250YHA
Indoor
Service Ref.
intake air
PEH-RP200MYA
(Airflow Rate
3
60m
/min)
PEH-RP250MYA
(Airflow Rate
80m
3
/min)
Indoor
Service Ref.
intake air
PEH-RP200MYA
(Airflow Rate
60m
3
/min)
PEH-RP250MYA
(Airflow Rate
80m
3
/min)
NOTE:
CA : Capacity (W)
[4] CORRECTION FACTORS
Cooling capacity correction factors
Service Ref.
5m
PEH-RP200MYA
1.00
PEH-RP250MYA
1.00
Service Ref.
45m
PEH-RP200MYA
0.898
PEH-RP250MYA
0.898
Heating capacity correction factors
Service Ref.
5m
PEH-RP200MYA
1.00
PEH-RP250MYA
1.00
Service Ref.
45m
PEH-RP200MYA
0.976
PEH-RP250MYA
0.976
Outdoor intake air
-10
DB˚C
CA
P.C.
15
14224
4.12
20
13664
4.47
25
13216
4.75
15
17145
4.96
20
16470
5.38
25
15930
5.72
Outdoor intake air
5
DB˚C
CA
P.C.
15
22624
6.28
20
21840
6.77
25
20608
7.19
15
27270
7.57
20
26325
8.16
25
24840
8.66
P.C. : Power consumption (kW)
Refrigerent piping length (one way)
10m
15m
20m
0.985
0.971
0.958
0.985
0.971
0.958
Refrigerent piping length (one way)
50m
55m
60m
0.887
0.876
0.865
0.887
0.876
0.865
Refrigerent piping length (one way)
10m
15m
20m
0.997
0.994
0.991
0.997
0.994
0.991
Refrigerent piping length (one way)
50m
55m
60m
0.973
0.970
0.967
0.973
0.970
0.967
WB˚C
-5
0
CA
P.C.
CA
15456
4.54
17248
14784
4.89
16352
14336
5.30
15680
18630
5.47
20790
17820
5.89
19710
17280
6.39
18900
WB˚C
10
15
CA
P.C.
CA
25536
6.98
28448
24640
7.54
27440
23744
8.06
26432
30780
8.41
34290
29700
9.08
33075
28620
9.71
31860
10.47
25m
30m
35m
0.943
0.931
0.919
0.943
0.931
0.919
65m
70m
75m
0.855
0.847
0.838
0.855
0.847
0.838
25m
30m
35m
0.988
0.985
0.982
0.988
0.985
0.982
65m
70m
75m
0.964
0.961
0.958
0.964
0.961
0.958
- 18 -
P.C.
5.24
5.65
6.14
6.31
6.81
7.40
P.C.
7.54
8.10
8.69
9.08
9.76
40m
0.908
0.908
80m
0.829
0.829
40m
0.979
0.979
80m
0.955
0.955