Daily Inspection And Periodic Inspection - Hitachi J300 Series Instruction Manual

J300 series
Hide thumbs Also See for J300 Series:
Table of Contents

Advertisement

Inspection
Inspection item
location
Overall
Ambient
Check ambient temperature,
environment
humidity, dust, corrosive
gases, oil mist, etc.
Devices overall
Check for abnormal
vibrations and noise.
Power supply
Check the input line voltage.
voltage
Main
Overall
(1) Insulation resistance test
circuit
(2) Check installation for
(3) Check for evidence of
(4) Clean.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Daily Inspection and Periodic Inspection (1/3)

Inspection cycle
Inspection content
Daily Periodic
(between main circuit
terminals and grounding
terminal)
looseness.
overheating in the various
components.
Inspection method
Criteria
Ambient temperature
between -10 to +50˚C;
no icing.
Ambient humidity 20 to
90%; no dew condensation.
Visual and aural
inspection.
Measure the voltage
No abnormalities.
between inverter
200 to 220 V, 50 Hz
terminals R(L1),
200 to 230 V, 60 Hz
S(L2) and T(L3).
380 to 415 V, 50 Hz
400 to 460 V, 60 Hz
No abnormalities in (1) and
(1) Increase tighting
Making a check
(2).
on the terque is
needed for the
Tightening torque (kgf.cm)
increase tighten-
• M3: 8 - 10
• M4: 12 - 15
ing of the modules
• M5: 20 - 25
such as a power
• M6: 25 - 30
module, diode
• M8: 100 - 135
module. Do not
• M10: 150 - 200
execute increse
tightening with
no torque gauge
Tightening torque for IPM
prepared.
and Diode modules
(kgf.cm)
• M4: 10-15
(2) Tighten.
• M5: 15-20
• M6: 20-25
(3) Visual
inspection.
Standard
Instruments
replacement
period
__
Thermometer
Hygrometer
Tester
__
500 V class
Megohm meter