G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal? (Refer to 10-6.1.)
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
OK. (Cause is poor contact.)
MUZ/MUY-GE09/12/15/18NA
Thermistor
Defrost (MUZ)
Discharge temperature
Fin temperature
Ambient temperature
Outdoor heat exchanger temperature
MUZ/MUY-GE24NA
Thermistor
Defrost (MUZ)
Discharge temperature
Fin temperature
Ambient temperature
Outdoor heat exchanger temperature
H Check of R.V. coil
MUZ-GE09/12/15/18/24NA
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
In case CN721 (MUZ-GE09/12/15/18NA)/CN602 (MUZ-GE24NA) is disconnected or R.V. coil is open, voltage is
generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil.
Check if CN721 (MUZ-GE09/12/15/18NA)/CN602 (MUZ-GE24NA) is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between
the compressor and the intelligent
power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch twice (HEAT mode).
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between
the compressor and the intelligent
power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Yes
No
Yes
Symbol
Connector, Pin No.
RT61
Between CN641 pin1 and pin2
RT62
Between CN641 pin3 and pin4
RT64
Between CN642 pin1 and pin2
RT65
Between CN643 pin1 and pin2
RT68
Between CN644 pin1 and pin3
Symbol
Connector, Pin No.
RT61
Between CN671 pin1 and pin2
RT62
Between CN671 pin3 and pin4
RT64
Between CN673 pin1 and pin2
RT65
Between CN672 pin1 and pin2
RT68
Between CN671 pin5 and pin6
Is there 208/230 VAC between CN721 (MUZ-
GE09/12/15/18NA)/CN602 (MUZ-GE24NA)
and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
Is there 230 VAC between CN721 (MUZ-
GE09/12/15/18NA)/CN602 (MUZ-GE24NA)
and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
39
Replace the thermistor except RT64. When RT64 is
No
abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
Inverter P.C. board
Inverter P.C. board
Yes
No
Board
Board
Replace the inverter
No
P.C. board.
Replace the inverter
Yes
P.C. board.