Outdoor Air Through Two Horizontal Ducts; Air From Other Indoor Spaces - A.O. Smith BTX 100 Instruction Manual

124 series; 125 series commercial gas water heaters
Hide thumbs Also See for BTX 100:
Table of Contents

Advertisement

1. 1 square inch per 3000 Btu/hr (733 mm
input rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.

outdoor aIr throuGh two horIZontal ducts

fIGure 6.
The confined space shall be provided with two permanent horizontal
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The horizontal ducts shall communicate directly with the
outdoors. See Figure 6.
Each duct opening shall have a minimum free area of 1 square inch
per 2,000 Btu/hr (1100 mm
per kW) of the aggregate input rating of
2
all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area
as the free area of the openings to which they connect. The minimum
dimension of rectangular air ducts shall be not less than 3 inches.

aIr froM other Indoor spaces

per kW) of the total
2
The confined space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. See Figure 7.
Each opening shall communicate directly with an additional room(s)
of sufficient volume so that the combined volume of all spaces
meets the criteria for an Unconfined Space.
Each opening shall have a minimum free area of 1 square inch per
1,000 Btu/hr (2200 mm
all appliances installed in the enclosure. Each opening shall not be
less than 100 square inches (645 cm
13
fIGure 7.
per kW) of the aggregate input rating of
2
).
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents