Wiring - Main Power; Wiring - Low Voltage Wiring; Figure 9 Common Wall Mounting Installations; Figure 10 Unit 24V Terminal Board - Bard CH3S1 Installation Instructions Manual

Wall mounted packaged heat pump
Table of Contents

Advertisement

FIGURE 9
COMMON WALL MOUNTING INSTALLATIONS
Closet Installation
Note: duct maybe in attic or
below rafters as shown.
Unit (outside)
Supply Air
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information
and maximum fuse or "HACR" type circuit breaker
size. Each outdoor unit is marked with a "Minimum
Circuit Ampacity". This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked "Use Copper
Conductors Only". These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or "HACR" type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out. This tab
will now line up with the slot in the door. When shut, a
padlock may be placed through the hole in the tab
preventing entry.
See "Start Up" section for important information on
three phase scroll compressor start ups.
Rafters
Duct
Finished Ceiling
Grille
Wall Sleeve
Raised Closet Floor
Grille
Return Air
MIS-2240
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers. All equipment leaves the
factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
TAP
240
208
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
FIGURE 10
UNIT 24V TERMINAL BOARD
C
G
Rc
Rh
Y1
Y2
B
C
G
B
R
Y1
Y2
C
R
G
Y
Y1
B
Factory Jumper
Nine (9) wires should be run from thermostat subbase to
the 24V terminal board in the unit. A nine conductor,
18 gauge copper color-coded thermostat cable is
recommended. The connection points are shown in
Figure 10.
IMPORTANT
Only the thermostat combinations as shown
above will work with this equipment.
TABLE 3
THERMOSTAT WIRE SIZE
T
a r
n
f s
r o
m
r e
V
A
F
L
A
W
5
5
2
3 .
RANGE
253 – 216
220 – 187
T7652H1000 THERMOSTAT
BARD PART #8403-052
L
W1
A1
1F93-380 THERMOSTAT
BARD PART #8403-049
W3/A1
W1
W2
E
W1
W2
W3
E
L
DH
O1
UNIT LOW VOLTAGE
TERMINAL BLOCK
MIS-2026 A
M
a
i x
m
u
m
D
s i
a t
n
c
e
i
e r
G
a
u
g
e
n I
F
e
t e
2
0
g
a
u
g
e
4
5
1
8
g
a
u
g
e
6
0
1
6
g
a
u
g
e
1
0
0
1
4
g
u
a
g
e
1
6
0
1
2
g
u
a
g
e
2
5
0
Manual 2100-455A
Page
15 of 25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ch4s1Ch5s1

Table of Contents