Bacnet Objects Supported - Honeywell TB7200 Integration Manual

Tb7200 & tb7300 series bacnet thermostats with occupancy sensor
Table of Contents

Advertisement

BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS

BACNET OBJECTS SUPPORTED

Device Objects
Type and
Object Name
Instance
TB7200X5x14B
Device
TB73xxX5X14B
63-4524—02
Table 4. Device Objects.
Object Property
Object_Identifier
Property 75 (R,W)
Object_Name
Property 77 (R,W)
Model Name
Property 70 (R)
Firmware Revision
Property 44 (R)
Protocol Version
Property 98 (R)
Protocol Revision
Property 139 (R)
Max ADPU Length
Property 62 (R)
ADPU Timeout
Property 10 (R)
Application-Software-
Version Property 12 (R)
Max_Master (R,W)
MS/TP_Address
Property 1001 (R,W)
MS/TP_Baud_Rate
Property 1002 (R,W)
16
Thermostat Parameter
Unique ID number of a device on a network.
Unique name of a Device on a network.
Thermostat Model number.
Current BACnet firmware revision used by the
thermostat.
Current BACnet firmware protocol version.
Default is Version 1.
Current BACnet firmware protocol revision.
Default is Version 2.
Maximum ADPU Length accepted
Default is 244
ADPU timeout value
Default is 60,000 ms
Thermostat base application software version.
Default is based on current released version
Maximum master devices allowed to be part of the
network. 0 to 127, default is 127.
BACnet MS-TP MAC Address. Proprietary attribute.
Default is as assigned by configuration.
BACnet MS-TP Baud-Rate. Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4 KBps, 4
= 76.8 KBps and 5 = Auto Baud Rate. Index 5 is Write
only. Reading attribute will state current Baud rate used.
Writing index 1 to 4 will fix the Baud rate to the desired
value.