Getting Started - Honeywell TB7200 series User Manual

Zigbee wireless survey toolkit for tb7200/tb7300/tb7600 series thermostats
Table of Contents

Advertisement

ZIGBEE WIRELESS SURVEY TOOLKIT FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
NETWORK
FIELD WIRING
ELIMINATED

GETTING STARTED

Included in the TBST-5014W wireless survey kit, you will
find the following items:
• 2 ea. survey tools
• 2 ea. 120 Vac charger for the survey tools
IMPORTANT
Before performing a survey, please insure that
both survey tools are fully charged overnight.
The survey tool will display a numerical percentage value
on the LCD screen which represents the wireless network
ZigBee RSSI dBi value (Receiving Signal Strength
Indicator).
IMPORTANT
Please note that it is normal for the value to fl
uctuate slightly (up to 10-20%). The final reading
value is representative of the median averaged
values displayed.
• Any value from 10 to 100% indicates good ZigBee
connectivity.
• Any value below 10% may indicate that a repeater (TB-
RP5000W) may need to be installed.
Before you use the wireless survey toolkit to complete a
site survey, review this document to learn how to
configure the site survey tools and how to perform a site
survey using these tools.
About the Wireless Survey Tools
About The Survey Tools
• The survey tools feature an auto-shutdown after 10
minutes. After 10 minutes, 10 quick beeps will sound; if
the ON button is not re-pressed, the unit will shutdown
to prevent unnecessary battery drainage.
• The minimal expected battery life is at least 50 full
charge cycles. The maximum expected battery life is
200 full charge cycles.
• Contact Honeywell for replacement batteries. The
survey tools use a custom rechargeable battery type.
DO NOT USE regular rechargeable batteries for
replacement. Doing so MAY result in critical failure
and/or injury.
62-2024—03
HONEYWELL THERMOSTAT(S)
MAIN MESH CLUSTER
Fig. 1. TB7200, TB7300, TB7600 ZigBee Wireless Network.
MESH TOPOLOGY
WIRELESS NETWORK
TB-RP5000W
Configuring the Wireless Survey
Tools
1. Charge the survey tools overnight.
2. Press the red ON button on the top of each device.
The green ON LED will light and the LCD will dis-
play Signal % 254 then display Signal % 0. If the
devices have already been configured, the signal
strength reading will be greater than zero and very
likely 99 or 100 since the devices are in close prox-
imity to one another.
3. Press and hold the Override button for five seconds,
as shown in Fig. 2, until Com addr displays on the
LCD.
Fig. 2. Press the left (red) button.
4. Press the Override button once and PAN ID will dis-
play.
5. Assign the PAN ID with the up/down arrows on the
right, as shown in Fig. 3. Both devices should be
assigned the same PAN ID.
2
REPEATER
REMOTE HONEYWELL
THERMOSTAT(S) CLUSTER
M32554
M33045

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tb7300 seriesTb7600 seriesTbst-5014w