Refrigeration Cycle Diagram - LG LT-E1820CL Service Manual

Ceiling cassette air conditioner
Hide thumbs Also See for LT-E1820CL:
Table of Contents

Advertisement

Refrigeration Cycle Diagram

• HEAT PUMP
INDOOR UNIT
CAPI C1
CAPI C2
(
Pipe Size
Capacity
GAS
LIQUID
18K
5/8"
1/4"
24K
5/8"
1/4"
• Rated performance for refrigerant line length of: 7.5m
• If 18K Capacity is installed at a distance of 15m, 187.5g of refrigerant
should be added ....................................................(15-7.5)x25g
Liquid Side
Liquid Side
Gas Side
H/EX
Liquid Side
Gas Side
Gas Side
Length (m)
Elevation (m)
Max.
Rated
Rated
7.5
50
5
7.5
50
5
OUTDOOR UNIT
ACCUM.
VALVE REVERSING
COMPRESSOR
* Additional
refrigerant
(g/m)
Max.
30
25
30
30
–12–