to the compressor output. All other heat pump operating
modes will operate normally, and the accessory relay will
be off in all other operating modes.
Thermostat Inputs – Table 5 shows the resulting demand
from differing combinations of inputs.
Y1 – Y1 is the input for compressor stage 1 if DIP1.3 = on.
Y1 is the input for Cooling Stage 1 if DIP1.3 = off.
Y2 – Y2 is the input for compressor stage 2 if DIP1.3 = on.
Y2 is the input for Cooling Stage 2 if DIP1.3 = off.
W – If Y1 and Y2 are active and DIP1.3 = on, then W is the
input for Heating Stage 3. If Y1 and Y2 are not active and
DIP1.3 = on, then W is the input for Emergency Heat. If
DIP1.3 = off, then W is the input for Heating Stage 1.
O – O is the input for Reversing Valve Relay if DIP1.3 =
on and DIP1.4 = on. O is the input for Heating Stage 2 if
DIP1.3 = off. O is the input for "Heat Mode" if DIP1.3 = on
and DIP1.4 = off; this means that the thermostat outputs a
"B" call when in Heating Mode and does NOT have an "O"
output. The DXM2 Control will employ "Smart RV" control.
This ensures that the RV will only switch positions if the
thermostat has called for a Heating/Cooling Mode change.
G – G is the input for Constant Fan Operation.
NSB and Override – NSB is the input for Night Setback
Mode. When Digital NSB is selected via the Accessory
Relays Dipswitch inputs and the NSB input is connected to
Ground "C", then the appropriately confi gured Accessory
Relay is turned on to signal the digital thermostat to
Table 4: Thermostat Inputs With Resulting Demands
Mode
O
No Demand
ON/OFF
Fan Only
ON/OFF
Cooling 1st Stage
ON
Cooling 2nd Stage
ON
Cooling & Dehumidistat
1
ON
Dehumidistat Only
ON/OFF
Heating 1st Stage
OFF
Heating 2nd Stage
OFF
Heating 3rd Stage
OFF
Cooling input takes priority over dehumidifi cation input.
1
Above inputs assume DIP 1.3 is in the heat pump position, and DIP 1.4 is in the O position. When 1.3 is in the heat/cool position, Y1 & Y2 are used for
3
cooling inputs; W and O are used for heating inputs. When 1.4 is in the B position, the O column would be opposite logic.
N/A for single stage units; Full load operation for dual capacity units.
4
5
ON/OFF = Either ON or OFF; H/C = Either Heating or Cooling.
DXM2 UNIT CONTROLS
Thermostat Operating Modes
Input
3
G
Y1
Y2
W
4
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON/OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
Application, Operation, & Maintenance Manual
go to Night Setback Setpoints. Stated differently, when
confi gured for Digital NSB Mode, the Accessory Relay
directly tracks the NSB input.
Note: Digital Night Setback feature requires a
compatible thermostat. Contact the manufacturer for
information on compatible thermostats.
When Digital NSB is NOT selected via the Accessory
Relays Dipswitch inputs and a communicating thermostat
confi gured for night setback is not connected, when the
NSB input is connected to Ground "C", then Y1, Y2, W, O,
and G inputs are ignored. During this time period, if OVR is
momentarily connected to 24VAC, then Y1, Y2, W, O, and
G are once again monitored for 2 hours. After the 2 hour
override period, the DXM2 reverts back to ignoring Y1, Y2,
W1, O, and G, assuming the NSB input is still connected
to Ground "C". There will be a random start timer when
coming back from NSB Mode.
Note: The maximum number of DXM2Controls with
daisy-chained "NSB" terminals is 75. Also, the
maximum total wire resistance of the "NSB" wiring is
500 Ohms.
OVR – OVR is the input for Night Setback Override or
Night Low Limit Staged Heating input (NLL). When Digital
NSB is NOT selected via the Accessory Relays Dipswitch
inputs and a communicating thermostat confi gured for night
1st stg
H / DH
RV
Fan
OFF
ON/OFF
OFF
OFF
ON/OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
13
DXM2 Controls
Output
2nd stg
AUX
Reheat
H/C
H/C
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON/OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents