MODEL NUMBER: SU7500RT3U1TF
Description
7,500 VA (7.5kVA) on-line, double-conversion UPS system for critical server, network and telecommunications
equipment. Installs in only 8 rack spaces (3U power module, 3U battery pack and 2U step-down transformer).
Maximum installed rack depth of 32.5 in. Expandable battery runtime with optional BP240V10RT3U and
BP240V32 external battery packs. Full-time sine wave 208 and 120V +/-2% output. Actively converts raw
incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates
continuously without using battery power during brownouts to 156V and overvoltages to 276V. Standard 3-wire
208V hardwire input connection; NEMA L6-30R, L6-20R and Nema 5-15/20R output receptacles. Detachable
input-output PDU module with manual bypass switch enables hot-swap UPS replacement without disrupting
power to connected equipment. Network-grade AC surge and noise suppression. Zero transfer time between AC
and battery operation. Network management interfaces support communications via RS-232, contact-closure
port and optional SNMPWEBCARD slot. Supports detailed monitoring of equipment load levels, self-test data
and utility power conditions via network interfaces. Includes PowerAlert monitoring software and complete
cabling. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface.
Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC
conversion, DC-to-AC conversion, bypass mode and output power status. LCD panel with scroll buttons offers
detailed diagnostic test information on startup and during self tests, plus real-time data on input and output
voltage, frequency (Hz), load percentage and battery charge level. LED/LCD display panel easily rotates for
viewing in rackmount or tower configurations. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post
rackmount accessories and 2-9USTAND tower kit included; 2POSTRMKITWM two post rackmount hardware
accessories available. Field replaceable, hot-swappable power module and external battery packs. Attractive
all-black color scheme. 2-year warranty and $250,000
service contracts available.
Features
7,500 VA (7.5kVA) on-line, double-conversion UPS system (High voltage input/High AND low voltage output)
Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without
powering off connected equipment
Installs in only 8 rack spaces (3U power module/3U battery pack/2U step-down transformer) with a maximum
installed depth of 32.5 inches
Offers 9 min. runtime at full load (7500VA/6000W) and 20 min. at half load (3750VA/3000W). Runtime is
expandable with any number of optional BP240V10RT3U external battery packs
Full-time sine wave 208V and simultaneous 120V +/-2% output
Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered
AC output
Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V
Standard 3-wire 208V hardwire input connection
2 x NEMA L6-30R, 2 x L6-20R and 12 x 5-15/20R output receptacles
connected equipment
insurance; extended warranty and
1 / 4
Highlights
7500VA on-line 8U rack/tower
UPS with expandable runtime
(3U Power Module + 3U Battery
Pack + 2U step-down
transformer)
Detachable PDU with manual
bypass switch enables hot-swap
UPS replacement without
powering off connected loads
Maintains 208V and
simultaneous 120V output
2% output voltage regulation over
an input voltage range of 156 to
276
Enhanced serial communications
ports, SNMP/Web Card Slot and
EPO interfaces
$250,000 Ultimate LIfetime
Insurance (USA & Canada only).
Applications
Ideal for protection of sensitive
electronics in any application
calling for upright tower or 19
inch rackmount UPS protection.
Common applications include
any mix of servers, workstations,
hubs, routers, concentrators, IP
telephony and traditional PBX
switching systems
Package Includes
3U power module with detachable
hot-swap PDU input/output panel
and bypass switch
3U external battery pack, 2U
step-down transformer
Three sets of 4 post rackmount
rails (one for each of the 2U and
3U components)
One set of tower stands for
upright tower configuration
PowerAlert software, complete
data cabling, user manual with

Advertisement

loading

Summary of Contents for Tripp Lite SU7500RT3U1TF

  • Page 1 On-line, double-conversion protection for UPS with expandable runtime mission-critical applications (3U Power Module + 3U Battery Pack + 2U step-down MODEL NUMBER: SU7500RT3U1TF transformer) Description Detachable PDU with manual bypass switch enables hot-swap 7,500 VA (7.5kVA) on-line, double-conversion UPS system for critical server, network and telecommunications UPS replacement without equipment.
  • Page 2: Specifications

    data cabling, user manual with Detailed LCD panel with scroll buttons offers detailed diagnostic test warranty information Network-grade AC surge and noise suppression Zero transfer time between AC and battery operation Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown, remote control and monitoring of UPS system and power data Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces.
  • Page 3 Half load runtime 20 min. (3750VA/3000W) Battery Pack Accessory (optional) BP240V10RT3U BP240V32 Connects to UPS via Included 3 wire DC cable Typical battery lifespan 4-6 years Battery charge Less than 8 hours to 90% (included battery set only) VOLTAGE REGULATION On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected Voltage regulation description nominal voltage at all times...
  • Page 4 (U.S., Canada & Puerto Rico) © 2014 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos may differ slightly from final products.