E. Combustible Mantel
See Figure 12.11.
A combustible mantel may be positioned no lower than 22 in. (508 mm) above the top of the fi replace opening.
A combustible mantel may have a maximum depth of 12 in. (305 mm).
Combustible trim and materials cannot be placed within 6 in. (152 mm) of the fi replace opening (top or sides).
Combustible materials projecting more than 1-1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the fi replace opening.
Combustible trim must not cover the metal surfaces of the fi replace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
Figure 12.11 Clearances to Mantels or other Combustibles above Fireplace
Combustible Wall
2 x 4 stud header
Standoffs
Notches
Heat & Glo • RUTHERFORD-42 • 4059-309 Rev G • 11/08
Combustible Decorative Facing
12 in./305 mm MAXIMUM
22 in./559 mm MINIMUM
Noncombustible
Decorative Facing
Measured from top of fireplace opening
Seal joint with
non-combustible sealant
7 ft (2134 mm)
minimum
floor to ceiling
45