TB7220 ULTRASTAT PROGRAMMABLE THERMOSTAT
Installer
Setup
Installer Setup
Number
Name
0270
CPH for Auxiliary
Heat
0280
Continuous
Backlight
0300
Changeover
0310
Deadband
Temperature
a
0320
Indication Scale
Daylight Saving
a
0330
0340
Remote
Temperature Sensor
0350
Heat Pump
Compressor Lockout
0360
Heat Pump Auxiliary
Lockout
0535
Temporary Occupied
Duration Limit
Number of Periods
a
0540
0580
Minimum
Compressor Off
Time
0600
Heat Temperature
Range Stops
0610
Cool Temperature
Range Stops
a
Setting available for modification in both the Installer and User setup modes.
63-2636—03
Table 6. Installer Setup Menu. (Continued)
Default
Setting
All Settings
9
1-12
0
0—No
1—Yes
1
0—Manual
1—Auto
3°F
2 (1.5)—2°F (1.5°C)
(2°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
0
0—°F
1—°C
2
0—Disabled
1—Enabled (US 1987)
2—Enabled (US 2007)
3—Enabled (Europe)
0
0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
0
0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
0
0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)
3
0—no duration
1—one hour
2—two hours
3—three hours
4—four hours
4
2—2 Periods
4—4 Periods
5
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
90
40 to 90°F (4 to 32°C)
50
50 to 99°F (10 to 37°C)
14
Notes
Only shown if multi-stage heat pump is selected (heat
pump with more heat than cool stages).
Always shown. If AC power not present the option is
overridden and normal backlight operation occurs.
Only shown if system has both heat and cool stages.
Only shown if Automatic Changeover Selected
Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).
Only shown for heat pump systems with more heat stages
than cool selected and remote sensor selection is outdoor
for control.
Must enforce a dead band between this and Auxiliary
Lockout
Only shown for heat pump systems with more heat stages
than cool selected and remote sensor selection is outdoor
for control.
Must enforce a dead band between this and Heat Pump
Compressor Lockout.
0 means no limit
Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the "Cancel
Period" option does not appear on the display.
Only shown if system has cool stages.
Only shown if system has heat stages.
Only shown if system has cool stages.