Control Wiring; Field Installed Accessories - Heat Controller HRE1318/1360-1A Installation And Operation Manual

Split system heat pump systems
Table of Contents

Advertisement

FIGURE 5
CONTROL WIRING FOR AIR HANDLER
Air Handler
W/BL
W2
G/BK
G
Y
Y
W/BK
W1
B
BL
G/Y
ODD
BR
C
R
R
Y
WIRING INFORMATION
Line Voltage
-
Field Installed
-
Factory Standard
18
TABLE 4
VOLTAGE RANGES (60 HZ)
Nameplate Voltage
208/230 (1 Phase)
208/230 (3 Phase)
460
575

13.3 CONTROL WIRING

(See Figure 5)
If the low voltage control wiring is run in conduit with the power supply, Class I insu-
lation is required. Class II insulation is required if run separate. Low voltage wiring
may be run through the insulated bushing provided in the 7/8 hole in the base
panel, up to and attached to the pigtails from the bottom of the control box. Conduit
can be run to the base panel if desired by removing the insulated bushing.
A thermostat and a 24 volt, 40 VA minimum transformer are required for the control
circuit of the condensing unit. The furnace or the air handler transformer may be
used if sufficient. See the wiring diagram for reference. Use Table 5 to size the 24
volt control wiring.
Heat Pump Thermostat
Y G W2
B
NOTE: RED WIRE REQUIRED WITH RANCO DDL DEMAND DEFROST CONTROL.
TABLE 5
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
(1) Wire length equals twice the run distance.
NOTE: Do not use control wiring smaller than No. 18 AWG between thermostat and outdoor unit.
TYPICAL THERMOSTAT:
HEAT PUMP WITH
C
E
R
ELECTRIC HEAT
SOLID COPPER WIRE - AWG.
3.0
16
14
2.5
16
14
2.0
18
16
50
100
Length of Run - Feet (1)
Operating Voltage Range at Copeland
Maximum Load Design Conditions for
Compressors
197 - 253
187 - 253
414 - 506
517 633
NOTES:
1. Jumper "E" to "W2" to
transfer control of
supplemental heat to
1st stage when the
emergency heat switch
is on.
2. This wire turns on heat
for defrost, omit for most
Heat Pump
economical operation.
Outdoor Unit
3. Wire with colored tracing
Y
stripe.
B
C
R
D
12
10
10
12
12
10
14
12
12
150
200
250
10
10
10
300