Gas Piping; Ga Piping - Weil-McLain GOLD CGa-25 Manual

Gold cga gas-fired water boilers
Table of Contents

Advertisement

GOLD CGa Gas-Fired Water Boiler — Boiler Manual
4

Gas piping

Connect gas supply piping to boiler
.
Table 4 Pipe capacity for 0.60 specific gravity natural gas
Capacity of pipe for pipe size of:
Gas pipe
(Capacity in cubic feet gas per hour)
length
(feet)
½"
10
132
20
92
30
73
40
63
50
56
75
45
100
38
150
31
¾"
1"
1¼"
278
520
1050
190
350
730
152
285
590
130
245
500
115
215
440
93
175
360
79
150
305
64
120
250
Natural Gas:
Propane Gas:
Gas supply piping
1½"
1600
1100
860
760
670
545
460
380
Part Number 550-101-009/0107