Purging method: to use vacuum pump

1 .Detach the service portis cap of 3-way valve, the valve
rod's cap for 2-way valve and 3-way valves, connect the
service port into the projection of charge hose (low) for
gaugemanifold. Then connect the projection of charge
hose (center) for gaugemanifold into vacuum pump.
2 .Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low) reach
vacuum condition in a moment, check 1 again.
3 .Vacuumize for over 15min. And check the level gauge
which should read -0.1MPa (-76 cm Hg) at low pressure
side. After the completion of vacuumizing, close the
handle 'Lo' in the vacuum pump. Check the condition of
the scale and hold it for 1-2min. If the scale-moves back
in spite of tightening, make flaring work again, then
return to the beginning of 3 .
4 .Open the valve rod for the 2-way valve to and an angle
of anticlockwise 90 degree. After 6 seconds, close the 2-
way valve and make the inspection of gas leakge.
5 .No gas leakage?
6 .Detach the charge hose from the service port, open 2-
way valve and 3-way. Turn the valve rod anticlockwise
until hitting lightly.
7 .To prevent the gas leakage, turn the service ports cap,
the valve rodis cap for 2-way valve and 3-way's a little
more than the point where the torque increases suddenly.
8 .Take the same steps from 1 to 7 for each ways to
ensure a completely vacuum for the whole system.
CAUTION: If the refrigerant of the air conditioner leaks,
it is necessary to make all the refrigerant out. Vacuumize
first, then charge the liquid refrigerant into air conditioner
according to the amount marked on the name plate.
In case of gas leakage, tighten
parts of pipe connection. If
leakage stops, then proceed 6
steps.
Open
Close
If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder.
12
Liquid stop valve
Gas stop valve
2 way valve
3 way valve
Gauge maifold(R410A)
Vacuum pump(R410A)
2 way valve
3 way valve
0
90
Service port
0
90
for 6 sec.
2 way valve
6
3 way valve
6
2 way valve
3 way valve
Valve rod cap
Valve rod cap
Service port cap
9.52mm
3 way valve
(3/8")
6.35mm
2 way valve
(1/4")
9.52mm
3 way valve
(3/8")
6.35mm
2 way valve
(1/4")
9.52mm
3 way valve
(3/8")
6.35mm
2 way valve
(1/4")
9.52mm
3 way valve
(3/8")
6.35mm
2 way valve
(1/4")
To indoor unit A
To indoor unit B
To indoor unit C
To indoor unit D