C7061M MINIATURE DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances. Therefore, this unit
may not exactly match the specifications listed. This
product is tested and calibrated under closely
controlled conditions, and minor differences in
performance can be expected if those conditions are
changed.
Models:
C7061M1008 - with 8 foot (2.4m) leadwires.
C7061M1016 - With connector.
Electrical Ratings:
The C7061 is powered from the Flame Safeguard unit that
delivers the necessary voltages to operate the tube and
shutter.
Ambient Operating Temperature Ratings
(Outside the Case):
-4°F to 175°F (-20°C to 80°C) using part no. 129464N UV
Sensing Tube.
Storage Temperature Ratings:
-4°F to 158°F (-20°C to 70°C).
Housing:
Violet, plastic cover.
Housing protection is IP66. Similar to Nema 4 (indoor, outdoor
protection; rain-tight, dust-tight, hose-directed water pro-
tection).
Pressure Rating of Quartz Viewing Window:
50 psi (350 kPa)
Mounting:
Threaded collar (internal 1-11 1/2 NPSM) internal threads for
attaching to a 1 inch sight pipe.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
65-0304—05
Wiring Connections: (C7061M1008)
Leadwire: NEC Class 1 color coded.
Length: 8 ft (2.4m).
Threaded Leadwire Faceplate Opening:
1/2-14 NPSM internal threads for attaching conduit (avoid
overtightening that could crack the housing).
Connector:
C7061M1016: Molex Woodhead 1R5006A20A120 (formerly
®
Brad Harrison
Type 41310).
Dimensions:
See Fig. 1.
Weight:
1.4 lbs (630 g).
Approvals:
Underwriters Laboratories Inc. Listed: MP268, Guide MCCZ2,
MCCZ8
Factory Mutual approved.
SwissRe (formerly Industrial Risk Insurers) Acceptable.
Replacement Parts:
129464N Ultraviolet Sensing Tube
Accessories:
123539 Antivibration Mount.
204341 Mirror Assembly.
105172C Pressure Sealoff adapter (3/4 in. npt)
118367 Swivel Mount
136733 Heat Block (3/4 in. npt)
SIL 3 Capable:
The C7061M when used with a R7861 Self Check amplifier in
relay module EC7810A, 20A, 30A, 40L, 50; RM7800 [E, G,
L, M], 30A, 38[A,B,C], 40[E,G,L,M], 50A, 88A, 90[A,B],
97[A,C], 98A is SIL 3 Capable in a properly designed
safety instrumented system. See Form number 65-0312
for certificate agreement.