Page 26
Jandy Pool Products, Inc., requires that the appli-
ance be connected to a "bonding loop" that includes all
electrical equipment in the system and on the equip-
ment pad. Bonding lugs must be connected with a
solid copper wire not smaller than 8 AWG (6 AWG in
Canada). Failure to do so will void the Jandy warranty.
Additionally, in the United States the National
Electrical Code (NEC) and in Canada the Cana-
dian Electrical Code (CEC), require that all metallic
components of a pool structure, including reinforcing
steel, metal fi ttings and above ground components be
bonded together (forming an "equipotential bonding
grid") with a solid copper conductor not smaller than
an 8 AWG (6 AWG in Canada).
The NEC and CEC also require that the equip-
ment and/or appliances associated with the pool water
circulating system, including, but not limited to, pump
motors and heaters, be bonded together as part of the
equipotential bonding grid. Jandy provides a special
labeled bonding lug on the right side of the heater to
accommodate this requirement.
6.4
Optional Pump Connection
(Maintain Temp Feature)
This optional feature allows the heater to turn
on the pool pump, bypassing the time clock setting,
to maintain the desired temperature. In order for the
MAINTAIN TEMP feature to be functional, a relay
INTERMATIC MODEL T104 MECHANICAL TIMER
NOTE:
INTERMATIC MODEL T104 (NOT PROVIDED WITH HEATER) WIRE CONNECTIONS SHOWN AS AN EXAMPLE,
OTHER MODELS MAY HAVE DIFFERENT CONNECTIONS. CONSULT TIMER MANUFACTURER FOR PROPER CONNECTIONS.
Figure 24. Example of Maintain Temp Wiring to the Time Clock
LXi
Pool/Spa Heater Installation and Operation Manual
(NOT PROVIDED WITH HEATER)
CLOCK
MOTOR
EQUIPMENT
GROUND
MAINTAIN TEMP (PUMP) RELAY
(SEE HEATER WIRING DIAGRAM)
must be installed and a dedicated line from the pool
pump time clock to the Maintain Temp (Pump) Relay
is needed. See Figure 24. The relay and pertinent
instructions can be obtained by ordering Jandy part
number R0467200.
6.5

Optional Remote Controls

RISK OF ELECTRIC SHOCK WHICH CAN RE-
SULT IN SERIOUS INJURY OR DEATH. Before
attempting installation or service, ensure that all
power to the device is disconnected/turned off at the
circuit breaker.
AVERTISSEMENT
RISQUE DE CHOC ÉLECTRIQUE POUVANT
CAUSER DES BLESSURES GRAVES OU LA
MORT. Avant de tenter l'installation ou d'utiliser le
service, assurez-vous que l'alimentation allant vers
le dispositif soit débranchée/éteinte au niveau du
disjoncteur du circuit. Branchez seulement à un
circuit protégé par un disjoncteur de mise à la terre.
Electrical wiring must be in accordance with the
latest edition of the National Electric Code (NEC),
ANSI/National Fire Protection Association (NFPA) 70,
unless local code requirements indicate otherwise.
4
2
L2
3
240 VAC
L1
1
FIELD INSTALLED COMPONENTS
OPTIONAL HEATER COMPONENTS
WARNING
PUMP