Manual Bypass Operation - Tripp Lite SmartOnline 5kVA Owner's Manual

Single-phase 5kva–6kva intelligent true on-line ups systems (rackmount/tower)
Hide thumbs Also See for SmartOnline 5kVA:
Table of Contents

Advertisement

Hot-Swap Power Module Replacement*
WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately
power down the UPS, resulting in the continued risk of death or injury from pontential contact with high voltage. The
UPS and detachable PDU are extremely heavy. This procedure requires several people to perform.
The UPS system includes an independent, detachable PDU with a Bypass Switch. This switch allows qualified service personnel to
remove the detachable PDU from the UPS for routine maintenance without disrupting power to connected loads. While this switch
is set to "BYPASS", connected equipment will receive unfiltered AC mains power. But the equipment will not receive battery power
in the event of a blackout.
* See manual included with SU12KRT4UHW Parallel PDU for Bypass.
UPS Removal (6kVA Single UPS Power Module Configurations Only)
STEP 1. Disable PowerAlert and disconnect the SNMP or serial USB communication cables from the communication ports
the UPS.
STEP 2. Press UPS's "OFF" button
in its LCD Display
button again to activate "BYPASS MODE".
STEP 3. Turn the detachable PDU's Bypass Switch
STEP 4. If an external battery module is connected to the UPS
The UPS is now safely powered down and it can be detached from the PDU to perform maintenance/replacement.
STEP 5. Remove the four screws that secure the front mounting ears of your UPS to the rack. With the PDU still attached, move
the UPS system and PDU forward in the rack slightly (approximately 4 inches), being sure that both components remain
adequately supported by the UPS's rackmount support rails.
STEP 6. At the rear of the UPS, remove the four screws that hold the detachable PDU to the UPS that is being serviced. With an
assistant holding the front of the UPS in place, carefully detach the PDU from the rear of the UPS and rest it on the UPS
support rails. Remove the UPS power module from the front of the rack.
WARNING! High voltage! Risk of electrical shock!
A
EPO
RS-232
PARALLEL
RS-232
USB
E
Steps 1, 3 & 4
, if the UPS is powered, until you hear a beep and see a "BYPASS MODE" message shown
B
on the front of the power module. You will be prompted to enter "BYPASS MODE". Press UPS "OFF"
C
to "BYPASS" on the rear of the UPS PDU.
D
, disconnect it from the UPS.
E
NORMAL
BY
PASS
D
13
C
Step 2
Step 5
Step 6
on
A
B