Download Print this page
Greenheck Combination Fire Smoke Dampers FSD-M211 Specifications
Greenheck Combination Fire Smoke Dampers FSD-M211 Specifications

Greenheck Combination Fire Smoke Dampers FSD-M211 Specifications

Combination fire smoke dampers steel 3v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating 4 hour fire resistance rating (bs476)

Advertisement

Quick Links

Application
Model FSD-M211 is a combination fire smoke damper with 3V style
blades. The FSD-M211 has been qualified to 10.2 m/s and 1 kPa for
operation and dynamic closure in emergency fire smoke situations.
Model FSD-M211 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Model FSD-M211 has also been tested in accordance with BS476 to
4 hours at Warrington Fire, UK, and is approved for fire partitions of
4 hours or less where British Standards are required.
Ratings
UL 555 Fire Resistance Rating
Fire Rating:
Dynamic Closure Rating: Actual ratings are size dependant
Maximum Velocity:
Maximum Pressure:
UL 555S Leakage Rating
Leakage Class:
Operational Rating: Actual ratings are actuator dependant
Maximum Velocity:
Maximum Pressure:
Max. Temperature:
BS476 Fire Resistance Rating
Fire Rating:
Standard Construction
Frame:
Blades:
Seals:
Closure Device:
Linkage:
Axles:
Bearings:
Size Limitations
Minimum Size:
Maximum Size:
Single Section:
Multiple Section:

Optional Features

• Stainless steel bearings
• 100°C, and 177°C RRL available (UL only)
• 69°C fusible link (BS476)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Sleeve with Integral flange on both sides available
• RRL/OCI (open close indication)
• TOR (remote override of 74°C or 100°C closure allows damper to
perform smoke management functions during a fire emergency)
Combination
1
1
Hours
2
10.2 m/s
1 kPa
I
10.2 m/s
1 kPa
177°C —Depending on actuator
4 hours
127mm x 25mm galv. steel hat
channel with reinforced corners . A
low profile head and sill are used on
sizes less than 432mm high to
maximize free area and
performance.
1.5mm galvanized steel, reinforced
with 3 longitudinal structurally
designed vee's.
Extruded silicone rubber blade
seals. Flexible stainless steel jamb
seals.
74°C RRL
Concealed in jamb.
13mm diameter plated steel
Bronze sleeve type.
101mm W x 101mm H
813mm W x 1270mm H
or 914mm W x 914mm H
3251mm W x 2540mm H Vertical
or 3658mm W x 2438mm H
Horizontal
FIRE SMOKE DAMPERS
UL 555 1
4 Hour Fire Resistance Rating (BS476)
Model FSD-M211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
ICBO Uniform Building Codes
SBCCI Standard Building Codes
British Standard BS476
Tested to 4 hours at Warrington Fire, UK
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
Standard 555 & 555S (Listing #R13317)
Greenheck Kunshan Co. Ltd. and Greenheck Fan
Corporation certifies that the model FSD-M211
shown herein is licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures
AIR
performed in accordance with AMCA Publication
PERFORMANCE
511 and comply with the requirements of the AMCA
AIR
Certified Ratings Programs. The AMCA Certified
MOVEMENT
AND CONTROL
Ratings Seal applies to air performance ratings only.
ASSOCIATION
®
INTERNATIONAL, INC.
H
* W & H dimensions furnished approximately 6mm undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
Model FSD-M211
Steel 3V Blades
UL 555S Leakage Class I
Hour Fire Resistance Rating
1
2
W
LH
RH

Advertisement

loading

Summary of Contents for Greenheck Combination Fire Smoke Dampers FSD-M211

  • Page 1: Optional Features

    “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standard 555 & 555S (Listing #R13317) Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model FSD-M211 shown herein is licensed to bear the AMCA Seal. The...
  • Page 2: Pressure Drop Data

    Pressure Drop Data This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 1.201 kg/m 3 . Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
  • Page 3 12.7 15.3 17.7 20.3 Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model FSD-M211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 4 12.8 15.3 17.7 20.3 Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model FSD-M211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 5 AMCA 5.5 Pressure Drop 1000 305mm x 305mm 610mm x 610mm Velocity Pressure Velocity (m/s) Drop (Pa) (m/s) 10.2 10.3 12.7 12.8 15.4 15.3 17.9 17.7 20.6 20.8 VELOCITY VS. PRESSURE DROP FACE VELOCITY- METERS/SECOND AMCA 5.5 914mm x 914mm Pressure Velocity Pressure...
  • Page 6: Specifications

    Tel: 0512-573-66666 • Fax: 0512-573-78633 www.greenheck.com 152mm Varies 127mm 305mm * "A" Dimension in. (mm) Standard Maximum 7 3/16 (183) 12 (305) 12 (305) 12 (305) Copyright © 2008 Greenheck Fan Corporation FSD-M211 Rev. 6 January 2008 38mm ma 95mm 137mm 127mm Sleeve Length...