Electric Heater Application/Operation - Greenheck HRE-20 Installation, Operation And Maintenance Manual

Heat recovery unit with evaporative cooling
Hide thumbs Also See for HRE-20:
Table of Contents

Advertisement

ELECTRIC HEATER APPLICATION/OPERATION

Factory installed electric heaters can be provided for preheat and/or post-heat (see FIGURE 11). An electric
preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. An electric
post-heater warms the air leaving the energy recovery wheel to a user specified discharge temperature. Electric
heaters are available in 208, 230, or 460 Vac (refer to heater nameplate for voltage).
Preheaters:
Preheaters are standard as 2-stage, step control. Step control heaters are designed with
multiple stages made up of equal increments of heating capability. For example, a 10 kW
heater with two stages will be composed of two 5-kW stages. Preheaters are single point
wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the
outdoor airstream after the preheater to turn the preheater on. See FROST CONTROL
APPLICATION/OPERATION for typical set points. If the outdoor air temperature falls below the
set point, the first stage of the preheater will turn on. If the first stage does not satisfy the set
point, the second stage will also turn on.
Post-heaters:
Post-heaters are standard as 4-stage, step control. Post-heaters are not single point wired
(see ELECTRICAL CONNECTIONS, page 5). The functionality of a 4-stage heater is the same
as the 2-stage preheater above, except it has an additional two stages of heat control.
Post-heaters supplied with Greenheck temperature control package are 3-stage with binary
control that provides 7 steps of heating. For example, a 35 kW heater with three stages will be
composed of 5, 10, and 20 kW stages. The stages essentially 'mix and match' to provide heat
output from 5 kW to 35 kW, in 5 kW increments.
FIGURE 11
12
Electric Preheater
The preheater is single point
wired to the HRE control
center. Access to the
preheater control panel is
through the supply filter door.
Disconnect
Post-Heater Control Panel
The post-heater is not single point
wired to the HRE control center.
Separate power must be supplied
to the post-heater disconnect.
Access to the post-heater control
panel is through the exhaust filter
door. The top portion of the indirect
evaporative cooling media must be
removed from the unit along with
the exhaust filters.
Electric Post-Heater

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hre-45Hre-55Hre-90

Table of Contents