3.7.3.1 Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
3.7.4

OVERSPEED

This feature protects the generator from damage by
shutting it down if it happens to run faster than the
preset limit. This protection also prevents the gener-
ator from supplying an output that could potentially
damage appliances connected to the generator cir-
cuit. Contact the nearest Generac Authorized Dealer
if this failure occurs.
4.1

FUSE

The generator panel's 15 amp fuse (Figure 4.1) protects
the DC control circuit against overload. The fuse is
wired in series with the battery output lead to the panel.
If the fuse element has melted open, the engine cannot
crank or start. Replace the fuse using only an identical
15-amp replacement.
The generator panel's 5 amp fuse protects the battery
charge circuit against overload. If the fuse element has
melted open, battery charging will not be possible.
Replace the fuse using only an identical 5 amp replace-
ment. To remove fuse, push cap down and rotate coun-
terclockwise.
Figure 4.1 – Generator Control Panel
FUSE
5A
AUTO
OFF
MAN.
FUSE
SET
15A
EXERCISE
TIME
4.2
CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see "Specifications," Section 1.5.
For engine oil recommendations, see Section 4.3.1.
To check the engine oil level, proceed as follows
(Figure 4.2):
1. Start the generator by moving the Auto/
Off/Manual switch to the MANUAL position. Allow
it to run for a short while and then shut it down
by moving the switch to the OFF position.
2. Remove the dipstick and wipe it dry with a
clean cloth.
Generac Air-cooled 7 kW, 12 kW and 15 kW Generators
R
L o c a t e y o u r n e a r e s t
d e a le r a t :
R
POWER SYSTEMS, INC.
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
F L A S H IN G G R E E N L E D =
N O U T IL IT Y
S E N S E
4
F L A S H IN G R E D L E D S =
E X E R C IS E R N O T S E T
Section 4 — Maintenance
3. Install the dipstick; then, remove it again. The oil
level should be at the dipstick "Full" mark. If nec-
essary, add oil to the "Full" mark only. DO NOT
FILL ABOVE THE "FULL " MARK.
Never operate the engine with the oil level
!
below the "Add" mark on the dipstick. Doing
this could damage the engine.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its origi-
nal position.
Figure 4.2 — Oil Dipstick and Fill, 7 kW
Oil Dipstick and Fill
Figure 4.3 — Oil Dipstick and Fill,
12 kW and 15 kW
Oil Dipstick
4.3

CHANGING THE ENGINE OIL

4.3.1 ENGINE OIL RECOMMENDATIONS

Use oil of American Petroleum Institute (API) Service
Class SG, SH or SJ. Use all season SAE 5W-30
Synthetic oil. Organic break-in oil is required before
using synthetic oil.
Generac
Oil Fill
®
Power Systems, Inc. 17