Section 3 - Operation; Control Console Components; Manual Transfer And Startup - Generac Power Systems QuietSource 005028-0 Owner's Manual

15kw/20kw/25kw liquid-cooled, prepackaged standby generators
Hide thumbs Also See for QuietSource 005028-0:
Table of Contents

Advertisement

3.1
CONTROL CONSOLE
COMPONENTS
The components of a home standby generator control
console (Figure 3.1) are as follows:
Figure 3.1 - Generator Control Console
OVER CRANK
OVER SPEED
LOW COOL. LEVEL
HI COOL. TEMP.
LOW OIL PRESS.
LOW BATTERY
LED INDICATORS:
SYSTEM READY
FLASHING GREEN LED = NO UTILITY SENSE
5 FLASHING RED LED'S = EXERCISER NOT SET
(IN AUTO MODE ONLY)
SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON
RED LED'S = INDIVIDUAL FAULT
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)
AUTO
OFF
OFF
ON
SET
MANUAL
EXERCISE
TIME
TO SET EXERCISER TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.
2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS
THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.
3.1.1 AUTO/OFF/MANUAL SWITCH
Use this three-position switch as follows:
• Set the switch to AUTO for fully automatic opera-
tion. See "Automatic Operation" (Section 3.6).
• Set switch to MANUAL position to crank and start
the generator engine.
• Set switch to OFF position to shut down an oper-
ating engine. With OFF selected, operation will not
be possible.
DANGER
With switch set to AUTO, engine can crank and
!
start suddenly without warning. Such automat-
ic start up normally occurs when utility source
voltage drops below a pre-set level. To prevent
possible injury that might be caused by such
sudden starts, set AUTO/OFF/ MANUAL switch
to OFF before working on or around the unit.
Then, place a "DO NOT OPERATE" tag on con-
trol console.
3.1.2 FAULT INDICATOR LEDS
(SEE CHART ON PAGE 16)
These red LEDs turn ON when one or more of the fol-
lowing engine faults occurs and the engine shuts
down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/Engine Speed Signal Fault
• High Coolant Temperature/Low Coolant Level
CAUTION
RISK OF ELECTRICAL SHOCK. DO NOT REMOVE COVER. NO USER SERVICEABLE
PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
CAUTION
FOR STAND-BY SERVICE CONNECT OUTPUT OF GENERATOR TO SUITABLY RATED
TRANSFER SWITCH IN ACCORDANCE WITH CANADIAN ELECTRICAL CODE, PART I.
TENTION: POUR L'ALIMENTATION DE RESERVE, CONNECTER LA SORTIE DE
ATRICE A UN COMMUTATEUR DE CALIBRE APPROPRIE, CONFORMENENT AU
CANADIEN DE L'ECTRICITE, PREMIERE PARTIE.
WARNING
CAN AUTOMATICALLY START AT ANYTIME WITHOUT NOTICE.
Y REMOVE FUSE ON CONTROL PANEL AND NEGATIVE BATTE
SERVICING.
WARNING
THIS EMERGENCY POWER SYSTEM IS DESIGNED EXCLUSIVELY FOR
OUTDOOR INSTALLATION ONLY!
USE OF SYNTHETIC OIL IS RECOMMENDED
0F2629

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators
See Section 1.7 for further explanation of engine pro-
tection functions.
3.1.3 15 AMP FUSE
This fuse protects the control console's DC control
circuit against electrical overload and is located
inside the control panel. If the fuse has melted open
because of an overload, engine cranking and startup
cannot occur. If the fuse needs to be replaced, use
only an identical 15-amp replacement fuse (type
ATO).
3.1.4 5 AMP FUSE
This fuse protects the battery charger against electri-
cal overload and is located inside the control panel. If
the fuse needs to be replaced, use only an identical 5-
amp replacement fuse (type ATO).
This fuse will not remove the + battery input
0E7193
power from the PCB when it opens. This means
the exercise timer will not be reset.
3.1.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to
start and exercise automatically. "See Weekly
Exercise Cycle" (see Figure 3.3 and Section 3.6).
3.1.6 SYSTEM READY LED
The System Ready LED (green) has two main pur-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.
The system ready LED will be OFF when the switch
is in the MANUAL or OFF positions.
The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.
This secondary function is only available with DIP
switch two in the OFF position (ATS - automatic
transfer switch application).
3.2
MANUAL TRANSFER AND
START-UP
To transfer electrical loads to the Standby (EMER-
GENCY) power source side and start the engine man-
ually, refer to the Owner's Manual of the particular
transfer switch.