Section 9 – Installation Drawings - Generac Power Systems 004373-2, 004626-1 Owner's Manual

Liquid-cooled, prepackaged standby generators 40 kw/single-phase w/ 200 amp transfer switch; 40 kw/single-phase w/ 200 amp transfer switch california emissions
Table of Contents

Advertisement

RECOMMENDED FUEL/ELECTRICAL STUB-UPS
(SEE TOP VIEW)
DESCRIPTION
AC LOAD LEAD CONDUIT
INSIDE STUB-UP FOR
FUEL CONNECTIONS
NOTE:
FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS
(SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM
MODIFICATIONS REQUIRED FOR
INSIDE STUB-UPS.
WEIGHT DATA
UNIT: 729.7 kg [1609 lbs]
STEEL COMPARTMENT: 208.6 kg [460 lbs]
UNITS: mm [INCHES]
965 [37.99"]
1160 [45.67"]
877 [34.51"]
REAR VIEW
Guardian Liquid-cooled 40 kW Generators
Installation Drawing – Drawing No. 0D5335
INSIDE
BASE
A1
(LEFT)
C
LIFTING EYE
(4 PLACES)
Section 9 — Installation Drawings
NOTES:
1. STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION
2. CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND
ENGINE AUTOMATIC START/STOP CONTROL WIRES PROVIDED IN
AC CONNECTION PANEL.
3. EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.
4. 12 VOLT NEGATIVE GROUND SYSTEM
BATTERY TRAY INSIDE DIMENSIONS: 178 X 342.5 [7" X 13.5"]
5. 2.5" I.D. FLEX EXHAUST
6. MAIN LINE CIRCUIT BREAKER.
7. DOORS MUST BE OPENED 90 DEG. TO BE REMOVED.
8. A1 MAY BE USED
FOR CIRCUIT BREAKER STUB-UP LOCATION.
9. SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT
DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.
ENGINE SERVICE CONNECTIONS
INLET NATURAL GAS = 3/4" NPT COUPLING
OIL DRAIN = 1/2" NPT COUPLING
EXHAUST OUTLET -
2.5" OD MUFFLER OUTLET
CENTER OF
GRAVITY
981 [38.62"]
1930 [75.98"]
RIGHT SIDE VIEW
Generac
(1) 12V BATTERY
SEE NOTE 4
158 [6.22"]
®
Power Systems, Inc. 57