Honeywell Class 320 Meter Installation Instructions Manual page 8

Class 320 advanced kwh/demand meter
Table of Contents

Advertisement

CLASS 320 METER
Temperature Range
Relative Humidity
Range
Altitude
Voltage Overload
Current Sensor
Overload
Pollution Degree
Standards
Installation
(Overvoltage)
Category
Measurement
Category
Enclosure Material
Display Readout
Standard Ranges
RS-485 Serial
Communications
Cable
Recommended
In-Line Fuse
62-0397-02
-20C to +50C
0-95% non-condensing
2000 meters maximum
+25% continuously: +100% For 20 cycles
100% for 1 minute
Degree 2 in accordance with IEC 664
EN 61326-1:2006 IEC 61010-1:2001, 2nd Edition
Category III
Category III
Type 1 JIC steel or Type 4X Rain Tight
LCD
2-Wire Delta 120 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 120/208 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 120/240 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 277/480 VAC: 100, 200, 400, 800,1600, 3200 Amp
2-Wire Wye 277 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 400 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 600 VAC: 100, 200, 400, 800,1600, 3200 Amp
Cable:
Input/output Voltage:
Cable Connector:
Circuit Input Isolation:
Max Cable Distance:
Max Network Nodes:
Baud Rate:
Manufacturer:
Mfg. Part No:
Rating:
8
UL-listed/rated/3-conductor,
300 VAC, stranded
conductors, 22-26 AWG.
Ground-isolated +/-5.4Vdc
Screw terminal termination
5.3kVAC
4000 feet
64 cabling nodes (including
master)
9600, 19200, 38400, 76800
Littlefuse
KLDR.100
100mA, time-delay, 600VAC
cartridge fuse