Top Vent Horizontal Venting Runs - Montigo M40DV-ST Installation & Operation Manual

See-thru gas fireplace
Hide thumbs Also See for M40DV-ST:
Table of Contents

Advertisement

Example:
A 10' section and an elbow used in conjunction with 3 ft. flex section
(PFL-3) will, when extended in a five foot chase, allow for a maxi-
mum horizontal run of twelve and one-half feet from the centre of
the fireplace to outside wall and a minimum of 7'6" when retracted in
opposite direction. (See Figure 14a and 14b.)
"D" flex sections and "E" solid sections may be used in conjunction
with one another to obtain different possible horizontal length instal-
lations. NOTE: Flex section must not exceed maximum horizontal
length of 3 feet. (See Figure 15.)
Figure 13. Short Horizontal Installation.
Figure 14a. Extended installation.
P/N XG0207
Installation
Figure 14b. Retracted Installation.
Figure 15. Horizontal flex installation.
M40DV-ST See-Thru Gas Fireplace
Top Vent
Page 11

Advertisement

Table of Contents
loading

This manual is also suitable for:

M40dv-st-iM40dv-st-fM40dv-st-mh

Table of Contents