Mitsubishi Electric MSH-A18ND Service Manual page 13

Split-type, heat pump air conditioners
Table of Contents

Advertisement

8-4. Trouble criterion of main parts
MSH-A18ND
MSH-A24ND
Part name
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12(main), RT13(sub))
Indoor fan motor(MF)
MSH-A18ND
INNER FUSE
145: CUT OFF
MSH-A24ND
INNER
PROTECTOR
135i 5: OPEN
Horizontal vane
motor(MV1)
Vertical vane
motor(MV2)
Check method and criterion
Measure the resistance with a tester.
(Part temperature 10˚C ~ 30˚C)
Normal
8 k" ~ 20 k"
Measure the resistance between the terminals with a tester.
(Part temperature 10˚C ~ 30˚C)
Color of
lead wire
MSH-A18ND
WHT – BLK
198 " ~ 214 "
BLK – RED
209 " ~ 227 "
Measure the voltage power ON.
Color of lead wire
BRN – YLW
(When fan revolved one time)
YLW – GRY
Measure the resistance between the terminal with a tester.
(Part temperature 10 C ~ 30 C)
Normal
282" ~ 306 "
Normal
MSH-A24ND
132 " ~ 144 "
152 " ~ 166 "
Normal
4.5 ~ 5.5V
0V 5V 0V
(Approx.)
13
Figure
MSH-A18ND
MAIN
AUX
FUSE
MSH-A24ND
MAIN
AUX.
P
RED
ROTOR
YLW
BRN
ORN
GRN
P
:INNER PROTECTOR

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msh-a24ndMr.slim msh-a18nd-s1Mr.slim msh-a24nd-s1

Table of Contents