Honeywell VisionPRO IAQ Installation Manual page 3

Touch-screen programmable thermostat
Hide thumbs Also See for VisionPRO IAQ:
Table of Contents

Advertisement

Available languages

Available languages

Installer setup
Setup function
0220
Stage 1 compressor
1cycle rate
0230
Stage 2 compressor
cycle rate
0240
Stage 1 heat cycle rate
(CPH= cycles per hour)
0250
Stage 2 stage heat
cycle rate (CPH)
0260
Stage 3 heat cycle
rate (CPH)
0280
Backlight
0300
Manual/Auto
changeover
0310
Auto changeover
deadband
0320
Temperature display
0330
Daylight savings
0340
Indoor temp.
sensor
0342
Outdoor temp.
sensor
0345
Dual fuel heat
pump control
0346
Dual fuel heat pump
upstage to furnace
timer (in hours)
0347
Droop temperature
0350
Heat pump
compressor lockout
0360
Heat pump
auxiliary lockout
0365
Discharge temp.
sensor
Settings & options (factory default in bold)
E
Auto Discover
**
[Other options: 1 to 6 CPH]
E
Auto Discover
**
[Other options: 1 to 6 CPH]
E
Auto Discover
**
[Other options: 1 to 12 CPH]
E
Auto Discover
**
[Other options: 1 to 12 CPH]
E
Auto Discover
**
[Other options: 1 to 12 CPH]
0
Backlight on for approx. 45 seconds after keypress
1
Backlight always on low intensity, full bright after keypress
0
Manual (User options: Heat/Cool/Off)
1
Automatic (User options: Heat/Cool/Auto/Off)
(System selects heat/cool based on indoor temp.)
3
Heat/cool settings 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1.5°C to 5°C)]
0
Fahrenheit
1
Celsius
2
Auto-change to daylight savings time (2007 and beyond, for
areas that use the new 2007 DST calendar)
1
Auto-change to daylight savings time (through 2006, and for areas
that do not use the new 2007 DST calendar)
0
Daylight savings time is turned off
0
Display temp. at thermostat location only
1
Display temp. at indoor sensor location(s)
2
Average between thermostat & sensor location(s)
E
Auto Discover
**
0
None
1
Remote sensor
1
Droop Control
**
0
No Droop Control
**
2
Droop Control with Aux Heat Lockout
1
1 hour
**
0
Off
[Other options: 0.5, 1.5, 2-6, 8, 10, 12, 14, 16 hours]
2
Default
[Other options: 2 to 5°F (1°C to 2.5°C)]
40
Default
0
No compressor lockout
[Other options: 5 to 60°F (-15°C to 15.5°C)]
0
No heat pump auxiliary lockout
[Other options: 5 to 65°F (-15°C to 18.5°C)]
E
Auto Discover
**
0
No
1
Yes
3
**
**
**
VisionPRO
IAQ
®
**See pages 6 & 7
69-1816EFS—09