Facility Setting (Cooling At Low Outdoor Temperature) - Daikin RXN15KEVJU Installation Manual

R410a split series
Hide thumbs Also See for RXN15KEVJU:
Table of Contents

Advertisement

CAUTION
When connecting the connection wires to the terminal board
using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fi res.
Strip wire end
to this point.
Good
3)
Pull the wire and make sure that it does not disconnect. Then fi x the wire in place with a wire stop.
Facility Setting
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)).
Never use it in a residence or offi ce (the space where there is a human).
Cutting jumper 6 (J6) on the circuit board will expand the operation range down to 5°F (–15°C). However it will stop if the
outdoor temperature drops below –4°F (–20°C) and start back up once the temperature rises again.
1)
Remove the 3 screws on the side and remove the top plate of the outdoor unit.
2)
Remove the drip proof cover.
3)
Cut the jumper (J6) of the PCB inside.
1) Remove the
3 screws.
CAUTION
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
Do not place humidifi ers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifi er might cause dew jumping from the indoor unit outlet vent.
Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
English
Excessive strip length
may cause electrical
shock or leakage.
Wrong
Drip proof cover
Stripping wire at terminal block
Top plate
2) Remove the drip
proof cover.
PCB
3) Cut jumper J6.
11