Horizontal Vent Tables And Figures - Lennox Hearth Products MLDVTCD-35NE Installation Instructions Manual

Merit series mldvtcd direct-vent contemporary design gas fireplaces
Hide thumbs Also See for MLDVTCD-35NE:
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MERIT
Use Table 8 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components Required
Termination Kit Only
Termination Kit and 6 In. Vent
Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and Tele-
scopic Section (SV4.5L12)
Table 8
HORIZONTAL VENT FIGURES/TABLES
Notes:
• Secure Vent™ components (rigid vent pipe and terminal) are shown
in the Figures; Secure Flex™ components (flexible vent pipe and
terminal) may also be used.
• Two 45 degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting Figures for 90
elbows, must be followed if 45 degree elbows are used.
• SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through a combustible floor or ceil-
ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
• It is very important that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of 1/4" rise per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or near level.
• The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run
of 20 feet except for installations where an elbow is the only vertical
vent section in the system (see Figure 29).
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT
WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE
SYSTEM. See Figure 29.
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
20
SERIES DIRECT-VENT CONTEMPORARY DESIGN GAS FIREPLACES • MODEL MLDVTCD-35 • INSTALLATION INSTRUCTIONS
®
Exterior Wall Thickness - inches (mm)
6 to 9-1/4 (152 to 235)
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
Note: See Figure 28 on Page 19 showing wall thickness
range when using SV4.5HT-2 termination kit.
WARNING
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table C
H Maximum
V Minimum
feet
(meter)
feet
(meter)
3
(0.914)
Elbow Only
Typical termination shown.
u
When using Secure Flex,
use Firestop/Spacer
SF4.5HF
See Table 8 on Page 20 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 29
- Top Vent -
ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE
Table D
V Minimum
H Maximum
feet
(meter)
feet
(meter)
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
When using Secure Flex,
use Firestop/Spacer
SF4.5HF.
Wall Firestop/Spacer
(SV4.5HF)
Typical termination shown.
See Table 8 on Page 20 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 30
- Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
H
V
u
Wall
Firestop/Spacer
(SV4.5HF)
Example: If 20 feet of (H) hori-
zontal vent run is needed, then
4 feet minimum of (V) vertical
vent will be required.
This table shows a 1(V) to
5(H) ratio. For every 1 foot of
vertical, you are allowed 5 feet
of (H) horizontal run up to a
maximum (H) horizontal run
of 20 feet.
H
Ceiling
Firestop/Spacer
(SV4.5VF)
V

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mldvtcd-35nmMldvtcd-35nm-fb

Table of Contents