f) LED Lights and Audible Alarm Safeties

The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup a 5 second delay occurs while the board conducts an internal
timer check. A beep occurs when the control switch is moved to the "ICE" position.
The green LEDs 1 through 4 energize and sequence from initial startup as listed in the
table below. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3,
2. For more information, see "II.B. Sequence of Operation."
Sequence Step
1 Minute Fill Cycle 4
Harvest Cycle
Last 50 seconds of harvest, WV de-energizes and PM energizes.
LEDs 1, 3, and 2 are on.
Freeze Cycle
Pump-Out Cycle
The built in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1
High Evaporator Temp.
(temperature > 127°F)
2
Harvest Backup Timer
(harvest > 20 min. for two
cycles in a row)
3
Freeze Timer
(freeze > specified setting
for two cycles in a row)
Timer is factory set using
S4 dip switch 9 & 10
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage
(92Vac±5% or less)
7
High Voltage
(147Vac±5% or more)
Legend: Comp–compressor; DV–drain valve; FMR–remote fan motor; FMS–self-contained
fan motor; F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.);
LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve;
WV–inlet water valve
Energized
LED
Components
WV
1, 4, and 2
WV, HGV,
Comp, FMR
1
Comp, PM,
FMR/FMS,
LLV
1, 4, 3, and
Comp, HGV,
2
SR, PM, DV,
FMR, WV
Type of Alarm
(53°C)
Time LEDs are On
Min.
2 minutes
20 minutes 3 to 5 minutes
5 minutes
freeze timer
setting
10 seconds 10 seconds 10 seconds
For proper operation, the pump-out timer
must remain in the factory default position.
Check for harvest problem (stuck HGV or
relay), hot water entering unit, stuck HM, or
shorted thermistor.
Check for open thermistor, HGV not opening,
TXV leaking by, low charge, or inefficient
Comp.
Check for F/S stuck closed (up), WV leaking
by, HGV leaking by, TXV not feeding properly,
low charge, HM not bypassing, or inefficient
Comp.
Red LED will turn off if voltage protection
operates.
The control voltage safeties automatically reset
when voltage is corrected.
20
Max.
Avg.
60 seconds
30 to 35 minutes
Notes