Download Print this page

Recommended Locations For Smoke Alarms; Locations To Avoid For Smoke Alarms - First Alert SA300 User Manual

First alert smoke alarm user's manual

Advertisement

RECOMMENDED LOCATIONS FOR SMOKE ALARMS

Installing Smoke Alarms in Single-Family Residences
The National Fire Protection Association (NFPA), recommends one
Smoke Alarm on every floor, in every sleeping area, and in every bed-
room. In new construction, the Smoke Alarms must be AC powered and
interconnected. See "Agency Placement Recommendations" for details.
For additional coverage, it is recommended that you install a Smoke
Alarm in all rooms, halls, storage areas, finished attics, and basements,
where temperatures normally remain between 40˚ F (4˚ C) and 100˚ F
(38˚ C). Make sure no door or other obstruction could keep smoke from
reaching the Smoke Alarms.
More specifically, install Smoke Alarms:
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with doors closed.
In the hall near every sleeping area. If your home has multiple sleep-
ing areas, install a unit in each. If a hall is over 40 feet (12 meters)
long, install an alarm at each end.
At the top of the first-to-second floor stairway, and at bottom of
basement stairway.
Specific requirements for Smoke Alarm installation vary from state to
state and from region to region. Check with your local Fire Department
for current requirements in your area. It is recommended AC or AC/DC
units be interconnected for added protection.
BEDROOM
BEDROOM
HALL
LIVING ROOM
KITCHEN
FINISHED BASEMENT
MULTI-STORY RESIDENCE
KEY:
RECOMMENDED
REQUIRED TO
FOR ADDITIONAL
MEET NFPA
PROTECTION
RECOMMENDATIONS
BEDROOM
HALL
BEDROOM
LIVING ROOM
KITCHEN
FINISHED BASEMENT
MULTI-STORY RESIDENCE
KEY:
BEDROOM
HALL
BEDROOM
RECOMMENDED
REQUIRED TO
FOR ADDITIONAL
MEET NFPA
PROTECTION
RECOMMENDATIONS
LIVING ROOM
KITCHEN
FINISHED BASEMENT
INSTALLING SMOKE ALARMS IN MOBILE HOMES & RVS
MULTI-STORY RESIDENCE
For minimum security install one Smoke Alarm as close to each sleeping
area as possible. For more security, put one unit in each room. Many
older mobile homes (especially those built before 1978) have little or no
insulation. If your mobile home is not well insulated, or if you are unsure
of the amount of insulation, it is important to install units on inside walls
only. Smoke Alarms should be installed where temperatures normally
remain between 40˚ F (4˚ C) and 100˚ F (38˚ C). WARNING: Test units
used in RVs after the vehicle has been in storage, before every trip,
and once a week while in use. Failure to test units used in RVs as
described may remove your protection.
BEDROOM
HALL
BEDROOM
LIVING ROOM
KITCHEN
FINISHED BASEMENT
MULTI-STORY RESIDENCE
DINING ROOM
BEDROOM
KITCHEN
LIVING ROOM
BEDROOM
SINGLE-STORY RESIDENCE, APARTMENT,
MOBILE HOME
SMOKE ALARMS WITH SILENCE
FEATURES RECOMMENDED FOR
ADDITIONAL PROTECTION
DINING ROOM
KITCHEN
BEDROOM
BEDROOM
LIVING ROOM
SINGLE-STORY RESIDENCE, APARTMENT,
MOBILE HOME
BEDROOM
SMOKE ALARMS
INTERCONNECTED
DINING ROOM
KITCHEN
WITH SILENCE
AC OR AC/DC
FEATURES
SMOKE ALARMS
RECOMMENDED
FOR ADDITIONAL
PROTECTION
LIVING ROOM
BEDROOM
SINGLE-STORY RESIDENCE, APARTMENT,
MOBILE HOME
DINING ROOM
BEDROOM
KITCHEN
LIVING ROOM
BEDROOM
SINGLE-STORY RESIDENCE, APARTMENT,
MOBILE HOME
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 (National Fire Code) Chapter 11
"For your information, the National Fire Protection Association's
Standard 72, reads as follows:"
"11.5.1 One- and Two-Family Dwelling Units."
"11.5.1.1 Smoke Detection. Where required by applicable laws, codes, or
standards for the specified occupancy, approved single- and multiple-
station Smoke Alarms shall be installed as follows: (1) In all sleeping
rooms Exception: Smoke Alarms shall not be required in sleeping rooms
in existing one- and two-family dwelling units. (2) Outside of each
separate sleeping area, in immediate vicinity of the sleeping rooms.
(3) On each level of the dwelling unit, including basements Exception: In
existing one- and two family dwelling units, approved Smoke Alarms
powered by batteries are permitted."
"A.11.8.3 Are More Smoke Alarms Desirable? The required number
of Smoke Alarms might not provide reliable early warning protection
for those areas separated by a door from the areas protected by the
required Smoke Alarms. For this reason, it is recommended that the
householder consider the use of additional Smoke Alarms for those
areas for increased protection. The additional areas include the base-
ment, bedrooms, dining room, furnace room, utility room, and hallways
not protected by the required Smoke Alarms. The installation of Smoke
Alarms in kitchens, attics (finished or unfinished), or garages is not
normally recommended, as these locations occasionally experience
conditions that can result in improper operation."
California State Fire Marshal (CSFM)
Early warning detection is best achieved by the installation of fire
detection equipment in all rooms and areas of the household as follows:
A Smoke Alarm installed in each separate sleeping area (in the vicinity,
but outside bedrooms), and Heat or Smoke Alarms in the living rooms,
dining rooms, bedrooms, kitchens, hallways, finished attics, furnace
rooms, closets, utility and storage rooms, basements, and attached
garages.

LOCATIONS TO AVOID FOR SMOKE ALARMS

For best performance, it is recommended you AVOID installing
Smoke Alarms in these areas:
Where combustion particles are produced. Combustion particles
form when something burns. Areas to avoid include poorly ventilated
kitchens, garages, and furnace rooms. Keep units at least 20 feet
(6 meters) from the sources of combustion particles (stove, furnace,
water heater, space heater) if possible. In areas where a 20-foot
(6 meter) distance is not possible – in modular, mobile, or smaller
homes, for example – it is recommended the Smoke Alarm be
placed as far from these fuel-burning sources as possible. The
placement recommendations are intended to keep these Alarms at
a reasonable distance from a fuel-burning source, and thus reduce
"unwanted" alarms. Unwanted alarms can occur if a Smoke Alarm is
placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
In air streams near kitchens. Air currents can draw cooking smoke
into the sensing chamber of a Smoke Alarm near the kitchen.
In very damp, humid or steamy areas, or directly near bathrooms with
KEY:
showers. Keep units at least 10 feet (3 meters) away from showers,
REQUIRED TO MEET
saunas, dishwashers, etc.
NFPA RECOMMENDATIONS
Where the temperatures are regularly below 40˚ F (4˚ C) or above
RECOMMENDED FOR
ADDITIONAL PROTECTION
100˚ F (38˚C), including unheated buildings, outdoor rooms, porches,
or unfinished attics or basements.
SMOKE ALARMS WITH SILENCE
FEATURES RECOMMENDED FOR
In very dusty, dirty, or greasy areas. Do not install a Smoke Alarm
ADDITIONAL PROTECTION
directly over the stove or range. Keep laundry room Smoke Alarms
free of dust or lint.
Near fresh air vents, ceiling fans, or in very drafty areas. Drafts can
blow smoke away from the unit, preventing it from reaching the
sensing chamber.
In insect infested areas. Insects can clog openings to the sensing
chamber and cause unwanted alarms.
Less than 12 inches (305mm) away from fluorescent lights. Electrical
"noise" can interfere with the sensor.
In "dead air" spaces. "Dead air" spaces may prevent smoke from
KEY:
reaching the Smoke Alarm.
REQUIRED TO MEET
NFPA RECOMMENDATIONS
Avoiding Dead Air Spaces
RECOMMENDED FOR
"Dead air" spaces may prevent smoke from reaching the Smoke Alarm.
ADDITIONAL PROTECTION
To avoid dead air spaces, follow the installation recommendations below.
SMOKE ALARMS WITH SILENCE
FEATURES RECOMMENDED FOR
On ceilings, install Smoke Alarms as close to the center of the ceiling as
ADDITIONAL PROTECTION
possible. If this is not possible, install the Smoke Alarm at least 4 inches
INTERCONNECTED AC OR
(102 mm) from the wall or corner.
AC/DC SMOKE ALARMS
For wall mounting (if allowed by building codes), the top edge of Smoke
Alarms should be placed between 4 and 12 inches (102 and 305 mm)
from the wall/ceiling line, below typical "dead air" spaces.
On a peaked, gabled, or cathedral ceiling, install the first Smoke Alarm
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally.
Additional Smoke Alarms may be required depending on the length,
angle, etc. of the ceiling's slope. Refer to NFPA 72 for details on require-
ments for sloped or peaked ceilings.
4

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Sa303Sa305