Download Print this page

Technical Specifications; Ordering Data - Firex 242 Specification Sheet

120v ac direct wire hearing impaired kit

Advertisement

120V AC
Direct Wire
Hearing
Impaired Kit
Smoke Alarm
Mounting
Brackets
Side
Views
Shipping Specifications
Individual Carton Dimensions
Master Carton Quantity
Master Carton Dimensions
Master Carton Weight

Ordering Data

Item No.
Kit Includes
41216 Smoke Alarm-
242
Model GC, 499 Relay,
and 240 Strobe
191 E. North Avenue
Carol Stream Illinois 60188 USA
Customer Service Telephone 1.800.951.5526
Customer Service Facsimile 1.630.260.7299
iccacustomerservice@invensys.com
www.FireXsafety.com
©2007 Invensys Controls
Strobe
4.5"
F
I
4.5"
R
E
2.375"
6-5/16" x 5-1/4" x 6-1/2"
1
6-5/16" x 5-1/4" x 6-1/2"
1.30 lbs.
Agency Listing
Packaging
UL
carton
3505 Laird Road Unit #14
Mississauga Ontario L5L 5Y7 Canada
Customer Service Telephone 1.800.387.7978
Customer Service Facsimile 1.905.828.1265
iccacustomerservice@invensys.com
Smoke Alarm

Technical Specifications

Product Weight
Operating Temperature
4.5"
Interconnect Qty.
Electrical Rating
Alarm Point
Horn Output
Listing
Detection Type
Humidity Range
Installation
This smoke alarm should be installed in accordance with the NFPA's
Standard 72 (National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269) and any local codes that apply.
For the AC and AC/DC direct wire smoke alarms, use #18 AWG
minimum solid or stranded wire. When interconnecting, maximum
wire length between any two is 1,500 feet for #18 AWG or 4,000
feet for #14 AWG (20 OHMS loop resistance).
DO NOT connect to any other type or model of heat or smoke alarm.
Connect smoke to a single AC branch circuit. If local codes do not
permit, be sure the neutral wire is common to both phases.
SMOKE
ALARM
WHITE
120 V
INPUT
BLACK
For Technical Service
Telephone 1.800.445.8299
Invensys
Facsimile 1.630.260.7243
trademarks of Invensys plc., its subsidiaries or
technicalservice@invensys.com
affiliated companies.
1.3 lbs.
40°F to 100°F (4°C to 38°C)
Up to 6 accessories in addition to 18
alarms. This signaling device can be
used only with the following FireX
smoke, Smoke/CO, and CO alarms: 406
(model G-6), 418 (model G-18), 484
(model PG-40), 5000 and 4618 (model
FADC), 4518 (model ADC), 4418 and
1018 (model AD), 4121 (model GC),
4480 (model PAD), 12000 (model
FADCM), 12400 (model GCM), 10000
(model COE), 10400 (model COEA).
These are low-voltage interconnect
alarms with a yellow interconnect wire.
120V AC, 60Hz, 264mA max.
1.1±0.47%/ft. obscuration
85 decibels at 10 feet
UL 217
Ionization
10% to 93% relative humidity
RELAY
N.C. (RED)
WHITE
COMMON (GRAY)
YELLOW
N.O. (BLUE)
BLACK
WHITE
®
, FireX
®
and Quick Connect™ are
STROBE
6/07 – 150-1499E

Advertisement