Technical Specifications - Hitachi HBU-2015 Instruction Manual

Dynamic braking unit
Table of Contents

Advertisement

C. HBU Series Technical Specifications
200 V SERIES
Input and output
specifications
Power supply
Indication
functions
Physical data
400 V SERIES
.
Input and output
Braking Activation Voltage 630/660/690/730/760V+-16V (jumper selectable) †
specifications
Power supply
Indication
functions
Physical data
* Peak current is defined as capacity for 10 seconds maximum, and 10% ED
† WARNING: It is critical to set jumper appropriately for the local supply voltage, or damage to the HBU, inverter and or resistors may result.
4
Model
Peak current (A) *
Continuous current (A)
Braking Activation Voltage
Maximum hysteresis
Multiple units
DC Bus Voltage Range
Power ON
Braking ON
Ambient temperature
Ambient humidity
Vibration
Protection
Weight
Model
Peak current (A) *
Continuous current (A)
Maximum hysteresis
Multiple units
DC Bus Voltage Range
Power ON
Braking ON
Ambient temperature
Ambient humidity
Vibration
Protection
Weight
Hitachi America, Ltd.
HBU-2015
50
15
380 ±10 VDC (not selectable)
~10 VDC
Maximum: 10 HBUs parallel connected
230-380V
The red "power" LED will be on whenever the
inverter DC Bus voltage is above ~35VDC
The green "braking" LED will be on during
braking unit conduction
Minus 10˚C to 40˚C (no frost)
90% RH (no dew)
10-20hz: 1g, 20-50hz: 0.2g
2.3 kg/5.1 lbs
HBU-4015 HBU-4030 HBU-4045 HBU-4220
25
50
8
15
About 16V
Maximum: 10 HBUs parallel connected
460-800V
The red "power" LED will be on whenever the
inverter DC Bus voltage is above ~35VDC
The green "braking" LED will be on during braking
unit conduction
Minus 10˚C to 40˚C (no frost)
90% RH (no dew)
10-20hz: 1g, 20-50hz: 0.2g
IP20
2.3 kg/5.1 lbs
Tarrytown, NY
HBU-2030
90
30
IP20
75
250
25
80
11.6 kg/
25.5 lbs

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hbu-2030Hbu-4030Hbu-4045Hbu-4015Hbu-4220